90
Sec
tion 5
App
e
ndic
e
s
E3NW-CRT
User’s Manual
Section 5
Command Descriptions and Data Formats
●
Zero Reset
This command sets the Zero Reset of the Sensor Amplifier Unit that corresponds to the
specified unit number.
●
Light OFF
This command turns OFF the light on the Sensor Amplifier Unit that corresponds to the
specified unit number.
●
Clear Light OFF
This command turns ON the light on the Sensor Amplifier Unit that corresponds to the
specified unit number.
●
Two-point Tuning First Point
This command executes tuning for the first point of two-point tuning for the Sensor
Amplifier Unit that corresponds to the specified unit number and output number.
●
Two-point Tuning Second Point
This command executes tuning for the second point of two-point tuning for the Sensor
Amplifier Unit that corresponds to the specified unit number and output number.
Tuning for the first point of two-point tuning must be executed first.
●
Position Tuning
The command executes position tuning for the Sensor Amplifier Unit that corresponds
to the specified unit number and output number.
Tuning for the first point of two-point tuning must be executed first.
●
Full Auto Tuning Setup
This command executes the full auto tuning setup for the Sensor Amplifier Unit that
corresponds to the specified unit number and output number.
●
Execute Full Auto Tuning
This command executes full auto tuning for the Sensor Amplifier Unit that corresponds
to the specified unit number and output number.
Wait at least 3 seconds after the full auto tuning setup is executed.
Bit
Description
Data
00
Zero Reset
0: Zero reset OFF
1: Zero reset ON
01 to 31
No applicable data
Always 0