86
Sec
tion 5
App
e
ndic
e
s
E3NW-CRT
User’s Manual
Section 5
Command Descriptions and Data Formats
●
Timer Time 1
This command reads or writes Timer Time 1 of the Sensor Amplifier Unit that
corresponds to the specified unit number and output number.
Timer Time 1 is assigned to the ON delay or one-shot timer.
●
Timer Time 2
This command reads or writes Timer Time 2 of the Sensor Amplifier Unit that
corresponds to the specified unit number and output number.
Timer Time 2 is assigned to the OFF delay timer.
●
DPC Setting
This command sets the DPC of the Sensor Amplifier Unit that corresponds to the
specified unit number.
Bit
Description
Data
00 to 15
Timer Time 1
Data range: 1 (00000001 hex) to 9999 (0000270F hex)
16 to 31
No applicable data
Always 0
Bit
Description
Data
00 to 15
Timer Time 2
Data range: 1 (00000001 hex) to 9999 (0000270F hex)
16 to 31
No applicable data
Always 0
Bit
Description
Data
00
Operating Mode
0: DPC OFF
1: DPC ON
01 to 31
No applicable data
Always 0
Содержание CompoNetT E3NW-CRT
Страница 1: ...CompoNet TM Digital Sensor Communications Unit E3NW CRT Cat No E430 E1 04 User s Manual ...
Страница 14: ...12 Introduction E3NW CRT User s Manual Introduction Reading This Manual ...
Страница 18: ...16 E3NW CRT User s Manual Introduction Contents Introduction MEMO ...
Страница 101: ......