V500/V520 Bar Code Reader Protocol
Appendix J
Log Data Clear (V500) (Sequence No. 359 (Hex 0167))
This sequence clears the log data.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Data Continuous Read (Scan) (V500) (Sequence No. 360 (Hex
0168))
This sequence performs the following operations repeatedly: Instructs the Bar Code Reader to start reading
and receives the data read by the Bar Code Reader. The scan notification method is used for the receive data.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data word allocation is similar to that of sequence No. 352 (Data read).
Note 1.
Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution
state until cancelled.
2.
Even if execution is cancelled, the Bar Code Reader still keeps reading. Execute sequence No. 351
(BCR read stop) to end the sequence.
Note The reception wait time is not set for this sequence.
Data Continuous Read (Interrupt) (V500) (Sequence No. 361
(Hex 0169))
This sequence performs the following operations repeatedly: Instruct the Bar Code Reader to start reading and
receives the data read by the Bar Code Reader. The interrupt notification method is used for the receive data
and the interrupt No. is 100.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
The receive data word allocation similar to that of sequence No. 352 (data read).
Note 1.
Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution
state until cancelled.
2.
Even if execution is cancelled, the Bar Code Reader keeps reading. Execute sequence No. 351 (BCR
read stop) to end the sequence.
3.
The reception wait time is not set for this sequence.
4.
Sequences No. 361 and No. 364 (Continuous Data Read with Interrupt) are not supported by the
CS1W-SCU21 and CJ1W-SCU41 Serial Communications Units. A protocol syntax error will occur if
an attempt is made to execute either sequence with a Serial Communications Unit.
BCR Initialize (V500) (Sequence No. 362 (Hex 016A))
This sequence clears the log data, confirms BCR connection and sets the BCR functions.
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of sequence No. 354 (BCR Function Set).
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Содержание CJ1W-SCU41
Страница 2: ...6 60 6 6HULHV 6HULDO RPPXQLFDWLRQV RDUGV DQG 6HULDO RPPXQLFDWLRQV 8QLWV 2SHUDWLRQ 0DQXDO 5HYLVHG 0D ...
Страница 3: ...KX ...
Страница 5: ...XK ...
Страница 9: ......
Страница 19: ......
Страница 119: ......
Страница 177: ......
Страница 187: ......
Страница 221: ......
Страница 259: ......
Страница 317: ......
Страница 333: ......
Страница 373: ......
Страница 395: ......
Страница 407: ......
Страница 443: ......
Страница 463: ......
Страница 501: ......
Страница 509: ......
Страница 513: ......
Страница 525: ......
Страница 526: ... XWKRUL HG LVWULEXWRU Cat No W336 E1 3 Note Specifications subject to change without notice Printed in Japan 0501 M ...