Error codes
Section 5-2
95
Clearing DM-configuration
errors
DM-configuration errors can be cleared by correcting the faulty settings in Data
Memory and consecutively transferring the new configuration data again to the
Unit. To transfer the configuration data you can choose from one out of two possi-
bilities:
• Turn the power of the CJ-series PLC system ON.
• Restart the Counter Unit (refer to section 4-1-2
5-2-2
IOWR/IORD-instruction errors
IOWR/IORD-instruction errors are detected by the Unit after they have been
issued from the ladder program to the Counter Unit. IOWR-instructions are used
to change Counter settings of the Unit. In case you specify faulty operands in the
IOWR-instruction the Unit reports this as an error. IORD-instructions only gener-
ate an error in case an invalid Control Code or an invalid number of words is spec-
ified.
Error Code 1
Error Code 2
Error
Description
0350
Invalid Control Code
Invalid Control Code
The Control Code, specified in the IOWR/IORD-
instruction is not supported by the Counter Unit. The
Invalid Control Code
is reported in Error Code 2.
0360
Control Code
Invalid number of
words
The number of words that is specified in the IOWR/
IORD-instruction is faulty. The
Control Code
of the
instruction for which the invalid number of words is
specified is reported in Error Code 2.
0400
Counter
No.
000
Z-Reset Mode Out of
Range
Two problems can cause this error. The Z-Reset
Mode that you specified is not in the valid range (0-
1). It is also possible that you issued an IOWR-
instruction to change the Maximum or Minimum
Count Value of a Circular or Linear Counter, causing
one or more of the already defined Range Limits or
Comparison Values to be outside the new Counting
Range.
Counter No.
indicates the number of the
Counter.
0412
Counter
No.
000
Invalid Counting
Range
The Lower Count Limit of the Counter is not a
negative value and/or the Upper Count Limit is not a
positive value.
0413
Counter
No.
000
Invalid Current
Counter Value
The Counter Value issued with the IOWR-instruction
is outside the counting range of the Counter.
Counter No.
indicates the number of the Counter.
0420
Counter
No.
Range No. Invalid
Range Limits
Upper Range Limit < Lower Range Limit.
Counter
No.
indicates the Linear Counter number and
Range
No.
indicates the Range number.
Содержание CJ1W-CTL41-E
Страница 2: ...i SYSMAC CJ series CJ1W CTL41 E 4 Channel Counter Unit Operation Manual Produced September 2004...
Страница 3: ...ii...
Страница 5: ...iv...
Страница 9: ...viii...
Страница 31: ......
Страница 43: ......
Страница 73: ......
Страница 119: ......
Страница 123: ......
Страница 126: ......
Страница 127: ......
Страница 131: ......
Страница 133: ...116...