140
B-2
Alarm messages
/i
Byte
Name
Description
0 to 1
Reference
The reference number of the sender.
2
Priority
The priority of the alarm.
3
Alignment
Reserved.
4 to 5
Type
The alarm type:
value 0003 Hex: Pull Alarm,
value 0004 Hex: Plug Alarm,
value 000A Hex: Plug Wrong Submodule.
6 to 9
API
The API.
10 to 11
Slot
The number of the slot having the alarm.
12 to 13
Subslot
The number of the subslot having the alarm.
14 to 17
ModuleIdent
The Ident number of the slot.
18 to 21
SubmoduleIdent
The Ident number of the subslot.
22 to 23
Specifier
The specifier of the alarm. The following bits are defined.
Bit:
Description:
0 to 10:
Sequence number
11:
Channel Diag exists (value 1 is exists)
12:
Manufacturer Diag (value 1 is exists)
13:
SubmoduleDiagState (value 0 is no error)
14:
Reserved
15:
AR Diag State (value 0 is no error)
24 to 25
Length
The length of additional data for Channel Related Diagnosis.