Troubleshooting using the IO Controller indicators
Section 8-2
117
Unit errors
/i
8-2-3-1 Unit errors
Startup errors
/i
Likely cause
During startup of the IO Controller it encountered a problem and can not
continue
IO Controller Unit response
The Unit will stop processing. There will be no error logged in the error log.
CIO Area Flags allocated to the IO Controller Unit
None of the bits is set.
Correction
Restart the IO Controller. Replace the IO-Controller if the error recurs.
Error category
Error
Indicators
Error log
(Hex)
7-segment
MS
NS
Unit errors
Startup errors
1 to 6
ON (red)
OFF
--
IO Controller
function
PROFINET configuration set invalid
C7
ON (green) Flashing
(red)
0202
PROFINET
Network errors
Ethernet failure
E3
ON (red)
OFF
020C
Bus hardware error
E5
0219
Memory access
errors
Special Unit error
--
Flashing
(green)
Flashing
(red)
0601
Memory access error
E9
0602
CPU Unit
Exchange
Backplane bus error
H0
Flashing
(red)
OFF
000E
Unit number duplication
H1
--
CPU Unit faulty
H6
--
I/O table not registered
H7
--
CPU Unit service monitoring error
HE
0001
CPU Unit watchdog timer error
HF
0002
Note
If Module Status is Red lit or flashing then refer to the displayed error code on the 7-
segment display for further information.
7-segment
MS indicator
NS indicator
Error log (Hex)
1 to 6
ON (red)
OFF
--
Содержание CJ1W-CRM21
Страница 1: ...CJ1W PNT21 PROFINET IO Controller Unit OPERATION MANUAL Cat No W12E EN 02 ...
Страница 2: ......
Страница 7: ...vii ...
Страница 16: ......
Страница 26: ...Basic operating procedure Section 2 4 10 ...
Страница 46: ...Installation of Configuration Software Section 3 5 30 ...
Страница 76: ...Generic IO Device DTM Section 4 4 60 ...
Страница 151: ...135 Index The index specifies the data related to a specific subslot to be read or written acyclically ...
Страница 156: ...140 ...
Страница 164: ...146 ...
Страница 168: ...150 ...
Страница 170: ...Section 152 ...