Rack-mount installation
When attaching to a rack, detach the rubber feet from the bottom surface of the unit.
When using an EIA 19-inch rack
When attaching to the rack, use BHP60P mounting brackets (sold separately) to connect the UPS body
with the battery unit. For details, refer to the instruction manual included with the rack-mount brackets
(BHP60P) and support angles (BUP06).
When using a JIS 19-inch rack
When attaching to the rack, use BHP60J mounting brackets (sold
separately) to connect the UPS body with the battery unit.
BUP06 support angles are not compatible with JIS standards.
Use a rack shelf.
For details, refer to the instruction manual included with the rack-
mount brackets (BHP60J).
For details, refer to the instruction manual included with the rack-
mount brackets (BHP60P) and support angles (BUP06). Support
angles are not compatible. Use a server rack.
2-2 Connecting the battery unit
Up to 5 battery units can be connected to the 1kVA-type BH100PCW.
Additional battery units also use the same model of BHM100PC (for 1kVA) as the first unit.
Use support angles (BUP06) to sup-
port each unit that is joined.
UPS
BH100PCW
Battery unit 1
BHM100PC
Battery units 2 to 5
BHM100PC
Max. total of 5
Run the battery cable through
the connector cover, connect
the cable, and screw
the connector cover shut.
*When adding a BHM100PC, remove the connector attached at shipment and connect the cable.
Each battery unit is equipped with a charging circuit.
The charging time does not increase when a battery unit is added.