3
If you notice an abnormal sound or smell, smoke or leaking fluid,
Immediately turn OFF the UPS power output switch (
), and disconnect the AC input plug from the wall outlet
(commercial power) and disconnect the battery connector (with Red and Black code) from the UPS rear panel.
If fluid leaks from the battery, do not touch it.
Doing so may cause blindness or burns.
If it touches your eyes or skin, wash it out with lots of clean water and consult your doctor.
Do not use the product in a closed place and/or do not cover the product.
Doing so may cause abnormal heating or a fire.
Do not pour water on the unit and do not allow it to become wet.
Doing so may cause an electric shock or a fire.
If the unit becomes wet, immediately stop using it and have it inspected and repaired.
When the battery replacement indicator starts to blink, or when the backup time
becomes shorter than the required time, immediately stop using the unit and
replace the battery pack.
Continuing to use the unit may cause a fire.
For more on how to check the battery, see ˝5. Maintenance and Inspection˝ on page 49 of the BH60PCW/
BH100PCW instruction manual.
Ambient temperature
Expected life
20°C
5 to 7 years
30°C
3 to 4 years
40°C
1.5 to 2 years
50°C
0.7 to 1 years
Caution (use)
Battery can be replaced while the unit is stopped only.
When replacing the battery, stop the connected devices, turn off the power supply (UPS) output switch
(
), and disconnect the AC input plug from the wall outlet.
Do not insert metal objects into the battery connectors.
Doing so may cause an electric shock.
Do not short the battery with metal objects.
Doing so may cause an electric shock, fire or burn.
Some electrical energy remains inside the spent battery.
Do not put the battery into fire.
The batteries may explode.
Replace batteries only with the same model and brand:
Battery pack models: BHB60PC: For BHM60PC battery unit (BH60PCW).
BHB100PC: For BHM100PC battery unit (BH100PCW).
Manufacturer: OMRON Corporation.
Using a battery other than that which is specified may cause a fire.
Risk of explosion if battery is replaced by an incorrect type.
Dispose of used batteries according to the instructions.
Do not use a new battery and an old battery at the same time.
Doing so may cause the battery to leak dilute sulfuric acid.
Caution (battery replacement)
* The values in the table on the left reflect the expected life under standard