Communication, Counter and Pulse
SECTION 4
4-1
PLC-setup Communication
4-1-1
RS-232C Port Communications Settings
The following settings are effective after transfer to the PLC.
If pin 2 of the 3G3MV-P10CDT Unit’s DIP switch is ON, communications
through the 3G3MV-P10CDT’s RS-232C port are governed by the default
settings (all 0) regardless of the settings in DM 6645 through DM 6649.
Word(s) Bit(s)
Function
00 to 03
Port settings
0: Standard (1 start bit, 7 data bits, even parity, 2 stop bits, 9,600 bps), Host Link unit
number:
0
1: Settings in DM 6646
(Any other setting will cause a non-fatal error and AR 1302 will turn ON.)
04 to 07
CTS control setting
0: Disable CTS control; 1: Enable CTS control
(Any other setting will cause a non-fatal error and AR 1302 will turn ON.)
08 to 11
Link words for 1:1 data link
0: LR 00 to LR 15 (Any other settings are ineffective.)
DM 6645
12 to 15
Communications mode
0: Host Link; 1: No-protocol; 2: 1:1 PLC Link Slave; 3: 1:1 PLC Link Master; 4: NT Link
(Any other setting causes a non-fatal error and turns ON AR 1302.)
00 to 07
Baud rate
00: 1,200 bps; 01: 2,400 bps; 02: 4,800 bps; 03: 9,600 bps; 04: 19,200 bps
DM 6646
08 to 15
Frame format
Start bits
Data bits
Stop bits Parity
00:
1 bit
7 bits
1 bit
Even
01:
1 bit
7 bits
1 bit
Odd
02:
1 bit
7 bits
1 bit
None
03:
1 bit
7 bits
2 bits
Even
04:
1 bit
7 bits
2 bits
Odd
05:
1 bit
7 bits
2 bits
None
06:
1 bit
8 bits
1 bit
Even
07:
1 bit
8 bits
1 bit
Odd
08:
1 bit
8 bits
1 bit
None
09:
1 bit
8 bits
2 bits
Even
10:
1 bit
8 bits
2 bits
Odd
11:
1 bit
8 bits
2 bits
None
(Any other setting specifies standard settings (1 start bit, 7 data bits; even parity, 2 stop
bits, 9,600 bps), causes a non-fatal error, and turns ON AR 1302.)
DM 6647
00 to 15
Transmission delay (0000 to 9999 BCD sets a delay of 0 to 99,990 ms.)
(Any other setting specifies a delay of 0 ms, causes a non-fatal error, and turns ON
AR 1302.)
00 to 07
Node number (Host Link)
00 to 31 (BCD)
(Any other setting specifies a node number of 00, causes a non-fatal error, and turns
ON AR 1302.)
DM 6648
08 to 11
Start code selection for no-protocol communications
0: Disables start code; 1: Enables start code in DM 6649
(Any other setting disables the start code, causes a non-fatal error, and turns ON AR 1302.)
39
Содержание 3G3MV-P10CDT-E
Страница 2: ...3G3MV P10CDT PLC Option Unit User s Manual Revised June 2003 ...
Страница 38: ...Unit Components and Specifications SECTION 2 2 1 4 Dimensions 68 128 55 25 ...
Страница 43: ......
Страница 85: ...Example Programs Appendix B 72 ...
Страница 86: ...Example Programs Appendix B 73 ...
Страница 87: ...Example Programs Appendix B 74 ...
Страница 88: ...Example Programs Appendix B 75 ...
Страница 90: ...Example Programs Appendix B 77 ...
Страница 91: ...Example Programs Appendix B 78 ...
Страница 97: ...Example Programs Appendix B B 4 9 Programs User_Parameter_Init 84 ...
Страница 98: ...Example Programs Appendix B 85 ...
Страница 99: ...Example Programs Appendix B User_Application Pos_Loop 86 ...
Страница 100: ...Example Programs Appendix B 87 ...
Страница 101: ...Example Programs Appendix B 88 ...
Страница 102: ...Example Programs Appendix B 89 ...
Страница 103: ...Example Programs Appendix B 90 ...
Страница 104: ...Example Programs Appendix B 91 ...
Страница 105: ...Example Programs Appendix B 92 ...
Страница 106: ...Example Programs Appendix B 93 ...
Страница 107: ...Example Programs Appendix B Pos_Home_Sequence 94 ...
Страница 108: ...Example Programs Appendix B 95 ...
Страница 109: ...Example Programs Appendix B 96 ...