4.3 Expansion Mode
In "Expansion Mode", one
CMC 430
test set works as "master unit", a second
CMC 430
test set works
as a current amplifier for the "master unit". That second
CMC 430
is the so-called "slave unit in
Expansion Mode".
The master unit is, as usual, connected to the computer either via USB, WiFi or Ethernet.
At the slave unit, link the ports PC and USB by means of the OMICRON-supplied USB cable.
CMC 430
master unit.
Use any EXPANSION PORT 1 ... 4.
CMC 430
slave unit in Expansion Mode.
Use EXPANSION PORT 2.
To configure this setup in the
Test Universe
software, launch the
Hardware Configuration
from the
test module you are presently working with.
On the
General
tab, at
Test Set(s)
select a
CMC 430
as test set.
In the drop-down list at
Amplifier(s) / Low Level Outputs / Sensor Simulation
you will find a
CMC 430
Current
entry. Select that entry to operate the
CMC 430
"slave unit" in Expansion Mode.
Click
Configure...
to set a current output configurations of your choice.
CMC 430 User Manual
46
OMICRON