710.1759.01.01-00D 

 

19/09/2018 

 

16 

You will find further information on safety precautions in the general warnings at the start of these 
instructions. 
  
Please note the following warnings in particular: 

 

Do  not  remove  (even  only  partially)  the  protective  panels  of  the  water  cooler  unless  it  is 
necessary.  

If the protective panels still have to be removed, disconnect the water cooler from its energy sources 
(electricity and water), and affix a sign stating “Maintenance work on water cooler in progress” on the 
operating panel. 
Replace the protective panels afterwards as quickly as possible. 

 

Wait at least 15 minutes before removing the protective panels so that the water cooler can cool 
down. Certain internal components have a very high and dangerous operating temperature!  

 
9.1   POSSIBLE ALARM SIGNALS AND THEIR RECTIFICATION 

 
9.1.1   CONTROLLER TYPE “A”, “D”, (CHA 1.3 TO CHA 129) 

 

No. 

Device 

status 

Alarm 

code 

Alarm 

description 

Possible cause 

Recommended actions 

Restore 

(*) 

Pump is 

working, 

solenoid 

valve is 

not 

working 

OFF 

Unit is in Off 
by remote 
ON/OFF 

Remote ON/OFF contact 
is open or internal bridge 
removed 

Check bridge ROO and close the 
contact 

OFF 

Unit in stand 
by 

The unit is energized but 
not switched on 

Follow procedure to start up the 
unit using button on controller 

LA2 

Antifreeze 
alarm 
(OPTIONAL) 

Set point is too low for 
actual system 

If possible increase set point, or 
check combination of flow, 
temperature and antifreeze 
percentage 

Liquid flow too low 

Check right rotation of pump and 
possible obstruction on liquid circuit 

P1 

Sensor P1 
defective  

Probe can be defective or 
not well connected 

Check connection and in case 
change probe 

Pump is 

not 

working, 

solenoid 

valve is 

working 

 

Pump is 
blocked 

The gear of the pump is 
blocked by dusty or 
corrosion 

Try to move the axe of the pump 
and after that switch on again 

The motor of the pump is 
internally protected 

Switch off the unit for one hour and 
try again after check the axe is not 
blocked and there are no liquid 
obstruction 

Fuses can be defective 

Check the fuses 

Pump and 

solenoid 

valve are 

not 

working 

CA 

Unit is in Off 
by remote 
ON/OFF  

Remote ON/OFF contact 
is closed 

Check bridge ROO and open the 
contact 

digital input 
alarm  

Liquid flow too low 

Check right rotation of the pump 
and possible obstruction on liquid 
circuit 

Liquid in the tank too low  Fill the tank 

Pump and 

solenoid 

valve are 

working 

HA 

High liquid 
temperature 
alarm 

Dirty heat exchanger 

Clean the heat exchanger as 
described in maintenance 

Solenoid valve is not 
working fine 

Check the solenoid valve 

Required cooling capacity 
is higher than nominal 

Decrease the required cooling 
capacity 

Water inlet temperature 
too high 

Check water inlet temperature 

LA 

Low liquid 
temperature 

Ambient temperature too 
low is decreasing liquid 
temperature 

The unit have to work in ambient 
condition as specified in this manual 

P2 

Sensor P2 
defective 

Probe can be defective or 
not well connected 

Check connection and in case 
change probe 

(*) 

A

 Automatic restore at standard recovery condition – 

M

 Restore the alarm on the controller using the following 

procedure 

Содержание CHA 1.3

Страница 1: ...voda voda CHA 1 3 to a CHA 129 English User and Maintenance Manual e tina Manu l k provozu a dr b Save These Instructions Tyto pokyny si uschovejte O M I srl Via dell Artigianato 34 Fogliano GO 34070...

Страница 2: ...ONNECTION 9 6 OPERATION 10 6 1 CHECK LIST FOR THE INITIAL START UP OF WATER WATER HEAT EXCHANGER SYSTEMS 10 6 1 1 CHECK LIST MODELS CHA 1 3 11 10 6 1 2 CHECK LIST MODELS CHA 24 60 11 6 1 3 CHECK LIST...

Страница 3: ...ion prevents the pump and other circuits parts damages The use of a water cooler is recommended for treatment of liquids in industrial civil or commercial cooling 2 GENERAL SAFETY INSTRUCTIONS SYMBOLS...

Страница 4: ...he electricity mains in accordance with the standard EN 60204 and must ensure compliance with all other applicable national standards Fire The electricity supply must be disconnected in the event of f...

Страница 5: ...water cooler cannot be switched on again until the cooling medium has been filled up to the MAX mark on the level display RA Tank heating The tank heating system warms up the water in the tank It can...

Страница 6: ...e of the cooling medium according to the preset value The temperature controller with digital display is integrated in the door of the switch cabinet Fault messages are displayed on the temperature co...

Страница 7: ...84 1 CHA 110 1325 760 1400 300 300 635 300 84 2 1 2 CHA 129 1325 760 1400 300 300 635 300 84 2 1 2 4 TRANSPORT PACKING STORAGE 4 1 REMOVING THE WATER COOLER FROM PACKAGING AND HANDLING Each water coo...

Страница 8: ...fumes dust or inflammable vapors with non explosive atmosphere and in any case free of any element that may affect its correct functioning A suitable area to ensure a constant temperature in all seaso...

Страница 9: ...ove the water cooler from the circuit switch it off or use it in different ways at the same time A pipeline system with integrated filter near the water cooler to protect the pump against solid matter...

Страница 10: ...the upright up to the gland on the base of the switch cabinet CHA 99 to CHA 129 Inside the switch cabinet lay the cable in the installation duct up to the main switch where it is connected directly C...

Страница 11: ...tion of the arrow on the casing If it is rotating in the opposite direction turn off the main switch of the cooler immediately and arrange for the polarity of the cooler to be reversed 14 After a few...

Страница 12: ...the supplement 6 2 OPERATING SETTINGS OF THE ELECTRONIC CONTROLLER All operations must be carried out by qualified personnel only The water cooler is supplied pre adjusted for normal operating condit...

Страница 13: ...de Meaning Standard value Set Set point 15 Hy Differential 3 For others parameters please contact the Manufacturer CONTROLLER TYPE D Instructions for changing the parameters required by the user To mo...

Страница 14: ...rcuit by closing the stop valves for the feed and return lines at the inlet and outlet as necessary Disconnect the machine from the cooling medium lines Empty the tank and the internal cooling medium...

Страница 15: ...tly isolate it from the electricity mains Disconnect the power cable Open the bypass valves if present for the liquid circuit and isolate the water cooler from the circuit by closing the stop valves f...

Страница 16: ...low too low Check right rotation of pump and possible obstruction on liquid circuit P1 Sensor P1 defective Probe can be defective or not well connected Check connection and in case change probe 2 Pump...

Страница 17: ...tton or the display shows HAL high temperature alarm or LAL low temperature alarm 2 Keep button pressed 3 The display shows rST which after 2 sec starts lightening to show that the values have been ca...

Страница 18: ...LSK OKRUH 25 5 2 2 P IPOJEN K ELEKTRICK ENERGII 25 6 PROVOZ 26 6 1 KONTROLN SEZNAM PRO PO TE N SPU T N V M N K TEPLA VODA VODA 26 6 1 1 KONTROLN SEZNAM PRO CHA 1 3 A CHA 11 26 6 2 PROVOZN NASTAVEN PRO...

Страница 19: ...ktrick ochrana zabra uje po kozen erpadla a dal ch st obvodu Pro pravu kapalin v pr myslov m civiln m nebo komer n m chlazen se doporu uje pou it chladi e vody 2 OBECN BEZPE NOSTN POKYNY SYMBOLY POU V...

Страница 20: ...hladic jednotka je vybavena hlavn m vyp na em Autorizovan mont n technik se mus postarat o to aby byla chladic jednotka p ipojena k p vodu elektrick ho proudu v souladu s normou EN 60204 a mus zajisti...

Страница 21: ...erpadla se vypnou Chladic syst m nelze znovu zapnout dokud nebude chladic m dium dopln no na MAXIM LN hranici na ukazateli hladiny RA Vyh v n n dr e Vyh v n n dr e oh v voda v n dr i Slou k dosa en op...

Страница 22: ...venou hodnotou Teplotn dic jednotka s digit ln m displejem je integrov na do dv ek sp nac sk n Chybov zpr vy se zobrazuj na teplotn dic jednotce v podob k d 3 4 2 DOPL KY ELEKTRICK OBVOD P ipojen kabe...

Страница 23: ...ADOV N 4 1 ODSTRAN N BALEN A MANIPULACE S CHLADIC JEDNOTKOU V echny chladic jednotky se dod vaj v zes len m kartonov m obalu na d ev n palet Chladic jednotka se mus za v ech okolnost nach zet ve vzp m...

Страница 24: ...Je nutn naj t vhodnou oblast ve kter teplota nebude klesat pod 2 C a rozhodn pak nesm p esahovat 40 C v dn m ro n m obdob kdy bude stroj v provozu Pokud chcete provozovat chladic jednotku p i teplot...

Страница 25: ...j vypnut nebo pou it jin m zp sobem Potrubn syst m s integrovan m filtrem pobl chladic jednotky k ochran erpadla p ed pevn mi sticemi a k zabr n n usazov n materi lu na tepeln ch v m n c ch Doporu en...

Страница 26: ...ou st sm rem k pr chodce na z kladn sp nac sk n CHA 99 CHA 129 Uvnit sp nac sk n polo te kabel do instala n ho veden k hlavn mu vyp na i ke kter mu se p ipojuje p mo Zkontrolujte zda jsou rouby na svo...

Страница 27: ...pn te hlavn vyp na na chladic jednotce a zajist te aby se polarita chladic jednotky p evr tila 15 Po n kolika minut ch znovu opatrn otev ete plnic roub a odstra te p ebyte n vzduch Pot roub znovu dot...

Страница 28: ...ELEKTRONICKOU DIC JEDNOTKU Ve ker pr ce na chladic jednotce sm j prov d t pouze odborn pracovn ci Chladic jednotka se dod v v nastaven pro norm ln provozn podm nky a obvykle nen nutn na n prov d t dn...

Страница 29: ...d V znam Standardn hodnota K d V znam Standardn hodnota Set Bod nastaven 15 Hy Diferencial 3 Ohledn ostatn ch parametr se obra te na v robce TYP DIC JEDNOTKY D P i zm n hodnoty BODU NASTAVEN postupuj...

Страница 30: ...stupu Odpojte stroj od veden chladic ho m dia Vypr zdn te n dr a vnit n okruhy chladic ho m dia 6 3 3 VY AZEN Z PROVOZU ZA ELEM P EPRAVY Ve ker pr ce na chladic jednotce sm j prov d t pouze odborn pra...

Страница 31: ...okud jsou p tomny okruhu kapaliny a izolujte chladic jednotku od okruhu t m e dle pot eby uzav ete ventily na p vodn m a v stupn m veden na vstupu a v stupu Odpojte chladic jednotku od veden chladic h...

Страница 32: ...nebo nen spr vn p ipojena Zkontrolujte p ipojen a p padn vym te sondu 2 erpadlo nefunguj elektromag netick ventil funguje erpadlo je zablokovan Zuby erpadla jsou zablokovan prachem nebo koroz Pokuste...

Страница 33: ...displeji zobraz HAL alarm vysok teploty nebo LAL alarm n zk teploty b Udr ujte tla tko stisknut c Na displeji se zobraz rST kter za ne po 2 sekund ch blikat a t m d najevo e hodnoty byly zru eny JAK V...

Страница 34: ...dchylka V 5 pro uveden hodnoty Standard operating conditions standardn provozn podm nky 10 2 HYDRAULIC CIRCUIT DATA VLASTNOSTI ERPADLA A N DR E Model Model Circulation pump Ob hov erpadlo Circulation...

Страница 35: ...a speci ln ch modelech chladic ch jednotek kter jsou dostupn na vy d n Propylene Glycol mixture Sm s propylenglykolu Glp 0 10 15 20 25 30 35 40 45 50 Tc C 0 3 5 7 10 13 17 21 26 32 Re 100 100 98 96 94...

Страница 36: ...PUMP 1 2 FUSES POJISTKY ERPADLA 1 2 SICHERUNG PUMPE 1 2 FUSIBILES BOMBA 1 2 FR1 2 HEATER 1 2 FUSES POJISTKY OH VA E 1 2 SICHERUNG KURBELWANNENHEIZUNG 1 2 FUSIBILES RESISTENCIA 1 2 FRA TANK HEATER FUS...

Страница 37: ...EMPERATURA ALTA SC HEAT EXCHANGER Tepeln v m n k W RMETAUSCHER INTERCAMBIADOR DE CALOR SCV FAN CONTROL PROBE Sonda zen ventil toru DRUCKAUFNEHMER VERFL SSIGUNGSDRUCK SONDA VENTILADOR SF VENT Otvor ENT...

Страница 38: ...Kapalina 8 Customer Spot ebitel 5 55 Ambient air Okolni vzduch Atm Customer Spot ebitel 2 40 13 INDIVIDUAL SPECIFICATION INDIVIDU LN SPECIFIKACE You will find the individual specification for the unit...

Отзывы: