68
NOTES:
1. For the control (parameter save) operation, a maximum of 5 sec is
required for the interval from receiving a command to completing the
operation. Before ending of that interval, never turn the power
for this device off (otherwise, the memory contents are destroyed
and disabled).
2. This unit requires a time length of 100 to 120mS as the interval from
completing reception of a command from the host before returning
the response. It also requires 20mS before it is able to receive the
next command after completing a reply.
Host Command
Time
100~120mS
Response
20mS
This device
Host Command