56
Set one type code in each digit (settings 1 to 4). When a code that is
not in the table is specified, it will be regarded as “no alarm (code: 0)”.
(A-group alarm)
Code
Type
No alarm
High limit absolute value
Low limit absolute value
Low limit absolute value
with holding feature
High limit deviation
Low limit deviation
Low limit deviation with
holding feature
High limit deviation
(inverted)
Low limit deviation (inverted)
Low limit deviation (inverted)
with holding feature
High/low limit deviation
High/low limit deviation with
holding feature
High/low limit deviation (inverted)
High/low limit deviation
(inverted) with holding feature
No alarm used
0
1
2
9
3
4
A
5
6
B
7
C
8
D
PV
PV
PV
PV
PV
PV
PV
PV
Alarm Set point
Alarm Set point
Alarm Set point
Alarm Set point
Alarm Set point
Alarm Set point
Set point
Set point
Set point
Alarm Set point
Set point
Alarm Set point
Set point
SV high limit absolute value
E
SV
Alarm Set point
SV low limit absolute value
F
SV
Alarm Set point
NOTE: SV high limit absolute and SV low limit absolute alarms can be
set only in the remote SV type.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание FUZZY LOGIC CN4800
Страница 2: ...M1791 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOUR...
Страница 47: ...45 ogy Group Quality Instrumentation Guaranteed 888 88 SOURCE...
Страница 100: ...98 MEMO ogy Group Quality Instrumentation Guaranteed 888 88 SOURCE...
Страница 101: ...99 MEMO ogy Group Quality Instrumentation Guaranteed 888 88 SOURCE...