59
4. Detection of the heater current requires the following current
transformer (to be purchased separately).
Heater current value
For 1~30A
For 20~50A
Types
CTL-6-SF
CTL-12-S36-8F
5. Heater break alarm is not available in the following cases.
1) Control output 1 is SSR drive output or current output.
2) Control output 1 is relay (1c contact) output and the heater is ON
on the contact N.C. (normally close) side.
3) The output proportion cycle time of control output 1 is lower than
20 seconds.