64
Operating procedure
(sub-set point)
Set the sub-Set point in parameter
. The target value is the
sub-Set point value while DI input is
on and, while it is off, the main Set
point value is the target value.
Main
Set point
Main
Set point
Sub-Set point
Target value
DI input
OFF
OFF
ON
Parameter to be used
Two set-points
* This function is an option.
Two set-points
Changes setpoint with external contact input (Digital Input). See “5.
Wiring” starting on the page 19 for connection of an external contact.
Main Set point
(SV)
Sub-Set point
( )
Target point
DI input
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание FUZZY LOGIC CN4800
Страница 2: ...M1791 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOUR...
Страница 47: ...45 ogy Group Quality Instrumentation Guaranteed 888 88 SOURCE...
Страница 100: ...98 MEMO ogy Group Quality Instrumentation Guaranteed 888 88 SOURCE...
Страница 101: ...99 MEMO ogy Group Quality Instrumentation Guaranteed 888 88 SOURCE...