Protection: Input overload 120 VAC max. for 15 sec. max.
6. CN63100 INDICATION ACCURACY
: ±(0.3% of Span +1°C) Includes
NIST conformity, cold junction effect and A/D conversion errors at 23°C
after 20 min. warm-up.
7. THERMOCOUPLE INPUT (CN63100 only)
:
Types: T, E, J, K, R, S, B, N, Linear mV, Software selectable
Input Impedance: 20 M
Ω,
all types
Lead resistance effect: 0.25
μ
V/
Ω
Cold junction compensation: Less than ±
1°
C (±1.
5°
C max.) error over 0 to
50°C max. ambient temperature range. Defeated for Linear mV
indication mode.
Resolution: 1° for all types, or 0.1° for T, E, J, K and N only.
TC TYPE
RANGE
WIRE COLOR
ANSI
BS 1843
T
-200 to +400°C
-328 to +752°F
(+) blue
(-) red
(+) white
(-) blue
E
-200 to +750°C
-328 to +1382°F
(+) violet
(-) red
(+) brown
(-) blue
J
-200 to +760°C
-328 to +1400°F
(+) white
(-) red
(+) yellow
(-) blue
K
-200 to +1250°C
-328 to +2282°F
(+) yellow
(-) red
(+) brown
(-) blue
R
0 to +1768°C
+32 to +3214°F
(+) black
(-) red
(+) white
(-) blue
S
0 to +1768°C
+32 to +3214°F
(+) black
(-) red
(+) white
(-) blue
B
+149 to +1820°C
+300 to +3308°F
(+) grey
(-) red
(+) none
(-) blue
N
-200 to +1300°C
-328 to +2372°F
(+) orange
(-) red
(+) orange
(-) blue
mV
-5.00 to +56.00
no standard
no standard
8. RTD INPUT (CN63100 only)
: 2 or 3 wire, 100
Ω
platinum, alpha =
0.00385 (DIN 43760), alpha = 0.0039162
Excitation: 150
μ
A typical
Resolution: 1 or 0.1 degree
Lead Resistance: 15
Ω
max. per input lead.
RTD TYPE
RANGE
385
-200 to +600°C
-328 to +1100°F
392
-200 to +600°C
-328 to +1100°F
OHMS
1.0 to 320.0
9. CN63300 RANGE AND ACCURACY
:
Input
Range
Accuracy*
(18 to 28 C)
Accuracy*
(0 to 50 C)
Impedance
Max.
Continuous
Overload
Resolution
10 VDC
(-1 to 11)
0.10% of
reading
+0.02 V
0.30% of
reading
+0.03 V
1M ohm
300 V
10 mV
20 mA DC
(-2 to 22)
0.10% of
reading
+0.03 mA
0.30% of
reading
+0.04 mA
10 ohm
100 mA
10 uA
*
Accuracies are expressed as
±
percentages after 20 minute warm-up. The
controller’s accuracy is specified in two ways: Accuracy over an 18 to
28°C range at 10 to 75% RH environment; and accuracy over a 0 to 50°C
range at 0 to 85% RH (non-condensing) environment. Accuracy over the
wide sensor range reflects the coefficient of the internal circuitry.
10. USER INPUT
: Internally pulled up to +5 VDC (1 M
Ω
). V
IN
MAX = 5.25
VDC; V
IL
= 0.85 V max; V
IH
= 3.65 V min; I
OFF
= 1
μ
A max.
Response time: 120 msec max
Functions: Program Lock
Integral Action Lock
Auto/Manual Mode Select
Setpoint Ramp Enable
Reset Alarms
Local/Remote Setpoint Select
Setpoint 1/Setpoint 2 Select
Serial Block Print
-75-
Содержание CN63100 Series