REFERENCE TABLES: CONFIGURATION PARAMETER MODULES
Configure Module 1 - Input Parameters (1-IN) CN63100
Display
Parameter
Range and Units
(Factory Setting)
Description/
Comments
tYPE
Input Type
tc-t - Type T TC
tc-E - Type E TC
tc-J - Type J TC
tc-k - Type K TC
tc-r - Type R TC
tc-S - Type S TC
tc-b - Type B TC
tc-N - Type N TC
LIN - Linear mV display
Thermocouple select
r385 - 385 curve RTD
r392 - 392 curve RTD
rLIN - Linear ohms display
(tc-J)
RTD select
SCAL
Temperature
Scale
°F/°C
(°F)
If scale is changed,
be sure to check all
parameters.
dCPt
Temperature
Resolution
0 or 0.0
(0)
If resolution changed,
be sure to check all
parameters.
FLtr
Digital Input
Filtering And
Display
Update
0 to 4
(1)
Increase number for
more filtering effect.
4 = 500 msec display
update rate. Adjusted
by Auto-Tune.
Display
Parameter
Range and Units
(Factory Setting)
Description/
Comments
SHFt
Input Signal
Shift (correction
offset)
-999 to 9999
1 or 0.1 degree
(0)
Normally set to 0.
SPLO
Setpoint Lower
Limit
-999 to 9999
0 or 0.1 degree
(0)
Set low limit
below high limit.
SPHI
Setpoint Upper
Limit
-999 to 9999
1 or 0.1 degree
(9999)
Set high limit
above low limit.
SPrP
Setpoint Ramp
Rate
0.0 to 999.9 degrees/minute
(0.0)
0.0 is off (no
ramping)
InPt
User Input *
PLOC - Program disable
ILOC - Integral action on/off
trnF - Auto/manual select
SPrP - Setpoint ramp on/off
ALrS - Reset alarm output(s)
SP2 - Select SP1/SP2
rSP - Select
Local/Remote
PrNt - Serial block print
(PLOC)
Low = lock
Low = off
Low = manual
Low = end ramp
Low = reset
Low = SP2
Low =remote
Low =block print
*
Model Number Dependent
-20-
These tables are only used for programming the CN63100 models.
Use the tables on page 21 if you are programming a CN63300.
Содержание CN63100 Series
Страница 23: ...FRONT PANEL PROGRAMMING CHART FOR CN63100 CN63300 CONTROLLERS 15 ...
Страница 48: ... 40 ...
Страница 62: ...PID Adjustments Cont d 54 Figure 33 Process Response Extremes ...
Страница 88: ... 80 ...
Страница 89: ... 81 ...
Страница 90: ... 82 ...