Block Read Command Byte Table
Locate the desired register combination for each Byte.
X=register to be printed. Use ASCII 0 for blank trailing byte locations.
For those programming in HEX: P = <50>, 0 = <30>, * = <2A>, $ = <24>
Byte1
Input
Setpoint
Output
Power
P Band
ASCII
HEX
X
1
<31>
X
2
<32>
X
X
3
<33>
X
4
<34>
X
X
5
<35>
X
X
6
<36>
X
X
X
7
<37>
X
8
<38>
X
X
9
<39>
X
X
A
<41>
X
X
X
B
<42>
X
X
C
<43>
X
X
X
D
<44>
X
X
X
E
<45>
X
X
X
X
F
<46>
Byte2
Integral
Time
Derivative
Time
Alarm 1
Alarm 2
ASCII
HEX
X
1
<31>
X
2
<32>
X
X
3
<33>
X
4
<34>
X
X
5
<35>
X
X
6
<36>
X
X
X
7
<37>
X
8
<38>
X
X
9
<39>
X
X
A
<41>
X
X
X
B
<42>
X
X
C
<43>
X
X
X
D
<44>
X
X
X
E
<45>
X
X
X
X
F
<46>
Byte3
Deviation
Offset
Power
Setpoint
Ramp
Cooling
Gain
ASCII
HEX
X
1
<31>
X
2
<32>
X
X
3
<33>
X
4
<34>
X
X
5
<35>
X
X
6
<36>
X
X
X
7
<37>
X
8
<38>
X
X
9
<39>
X
X
A
<41>
X
X
X
B
<42>
X
X
C
<43>
X
X
X
D
<44>
X
X
X
E
<45>
X
X
X
X
F
<46>
Byte4
Cooling
Deadband
Output
Status
Remote
Setpoint
Heater
Current
ASCII
HEX
X
1
<31>
X
2
<32>
X
X
3
<33>
X
4
<34>
X
X
5
<35>
X
X
6
<36>
X
X
X
7
<37>
X
8
<38>
X
X
9
<39>
X
X
A
<41>
X
X
X
B
<42>
X
X
C
<43>
X
X
X
D
<44>
X
X
X
E
<45>
X
X
X
X
F
<46>