Configure Module 2 - Output Parameters (2-OP)
Display
Parameter
Range and Units
(Factory Setting)
Description/
Comments
CYCt
Time
Proportioning
Cycle Time
0 to 250 seconds
(2)
0 turns O1 off. Set to
zero for Linear DC
output control. Not used
for ON/OFF Control.
OPAC
Output Control
Action
drct - cooling
rEv - heating
(rEv)
For both PID & ON/OFF
control.
OPLO
Output Power
Lower Limit
(Not used in
Manual Control)
0% to 100%, O1
(0)
Set OPLO < OPHI
-100% to 100%,
O1 & O2
(-100)
Negative % is only valid
for O2 cooling control.
OPHI
Output Power
Upper Limit
(Not used in
Manual Control)
0% to 100%, O1
(100)
Set OPHI > OPLO
-100% to 100%
O1 & O2
(100)
Negative % is only valid
for O2 cooling control.
OPFL
Sensor Fail
Power Level
(Not used in
Manual Control)
0% to 100%, O1
(0)
Select a level to safely
control the process in
the event of input
sensor failure.
CN63100 only.
-100% to 100%
O1 & O2
(0)
OPdP
Output Power
Dampening
(filtering) Time
0 to 250 seconds
(3) CN63100
(1) CN63300
0 = off (no dampening)
Set in range of 1/50 to
1/10 of integral time.
Adjusted by Auto-Tune.
Display
Parameter
Range and Units
(Factory Setting)
Description/
Comments
CHYS
ON/OFF Control
Hysteresis
1 to 250
(2) CN63100
(0.2) CN63300
For O1 ON/OFF
Control. Change to
Factory Setting prior
to Auto-Tune.
tcOd
Auto-tune
Dampening Code
0 to 2
(0)
0 = fastest response
2 = slowest response
ANtP
Main Linear DC
Output Range *
0 to 10 V
0 to 20 mA
4 to 20 mA
(4 to 20 mA)
Set linear output
range jumper to
match.
ANAS
Main Linear DC
Output Source *
OP
InP
SP
(OP)
SP = Active Setpoint
ANUt
Main Linear DC
Output Update *
0 to 250 secs
(0)
0 = Update rate of 0.1
sec.
ANLO
Main Linear DC
Output Low Scaling
Value *
-999 to 9999
(0.0)
Value depends on
ANAS assignment.
ANHI
Main Linear DC
Output High
Scaling Value *
-999 to 9999
(100.0)
Value depends on
ANAS assignment.
*