VALID CONTROL MODE COMBINATIONS
ON/OFF, PID, and Manual Control can be used for O1 (heat) and O2 (cool)
outputs according to the combinations below.
O1 & O2 VALID CONTROL MODES
O1 MODE
O2 MODE
MANUAL CONTROL
OUTPUT POWER
RANGE
O1 STATE O2 STATE
PID
—
0% to +100%
O1-TP
—
ON/OFF
(ProP = 0.0)
—
100%
O1-ON
—
Any other setting
O1-OFF
—
PID
PID
-100% to +100%
O1-TP
O2-TP
PID
ON/OFF
(GAN2=0.0)
0% to +100%
O1-TP
O2-OFF
-100% to 0%
O1-TP
O2-ON
ON/OFF
(ProP=0.0)
ON/OFF
(GAN2=0.0)
+100%
O1-ON
O2-OFF
-100%
O1-OFF
O2-ON
Any other setting
O1-OFF
O2-OFF
TP - Time Proportioning