following applies (only when the compressor is ON, otherwise the fan keeps its
minimum speed):
•
if Troom < Tset+3°C the fan is switched to minimum speed;
•
if Tset+3°C
≤
Troom < Tset+6°C the fan is switched to medium fan speed;
•
if Troom
≥
Tset+6°C the fan is switched to maximum fan speed.
At least 3 minutes must pass between one automatic speed change and another.
The display L1 shows the auto fan mode by cyclically switching the fan speed symbols as follows:
→
→
→
……
Ext fan motor and water disposal motor are always switched ON/OFF together with the compressor.
Compressor is switched ON for Troom
≥
Tset+Hy and is switched OFF for Troom
≤
Tset (unless the
defrosting function occurs).
The cooling defrosting subprogram, which starts with Troom < Tmin and finishes with Troom >
Tmin+2°C, forces the compressor, (and ext fan and water disposal motor outputs) to periodically switch
OFF and switch ON for Tp_off minutes (OFF state duration) and Tp_on minutes (ON state duration)
respectively.
When the defrosting function is active, the internal fan speed must be set as follows:
Fan speed
setting
Int. fan speed (compressor
OFF)
Int fan speed (compressor
ON)
Min
MED
MED
Med
MED
MED
Max
MED
MAX
The compressor (together with ext fan and water disposal motor) must be switched ON after a minimum
Rest_time delay (180 sec) from last circuit power-on or from any former compressor shutdown.
During this working mode all appliance’s malfunctions are enabled (see relative chapter below).
In cooling mode 4way valve output must always remain OFF.
on
on
Tset+Hy°
C
Tset
off