14 Warnings and alarms codes: 

 
 

At 

Diagnostic mode 

Fi’ 

Dirty filter warning 

2’ blinking 

Room sensor alarm 

3’ blinking 

Water level alarm 

8’ blinking 

Internal motor fan alarm 

13’ blinking 

EEprom data failure 

 
 
15 SPECIAL FUNCTIONS 
 
15.1 DIAGNOSTIC MODE: 
This function can be activated while the appliance is in STANDBY by pressing the keys SW4+SW5 on the 
display unit for at least 10 seconds. After that, the following sequence is started: 

 

all symbols of the display L1 are switched ON; 

 

D1, DP and D2 show the 1.1 SW release; 

 

D1 and D2 begin to show the code ‘At’ in blinking mode 

 

4way valve is turned on 

 

wait 1seconds 

 

the 4way valve is turned off 

 

(cooling mode) compressor, condensate water pump, indoor fan (max speed) and outdoor fan 
work (regardless Troom) 

 

wait 30seconds 

 

(heating  mode)  compressor,  4way  valve,  indoor  fan  (max  speed)  and  outdoor  fan  work 
(regardless Troom) 

 

In  Diagnostic  mode  all  the  alarms  are  enabled,  Defrost  and  Heatmax  functions  for  Heating  mode,  Defrost 
function for Cooling mode are enabled 
In Diagnostic mode, by pressing the SW6 button,  the room temperature acquired by the probe is shown on 
D1 and D2. 

 

Press the standby key SW1 or disconnect the power supply to quit Diagnostic mode 
 
15.2 AUTORESTART FUNCTION: 
The  board  must  store  in  EEprom  all  current  settings  (except  Sleep  mode  and  Timer  mode).  When  re-
powered after a power  mains interruption, it has to start up by recovering all previously stored settings (in 
case the DIAGNOSTIC function was enabled, after a black-out the appliance must set itself in STANDBY 
mode). In any case, compressor activation must be delayed by 3 minutes from each power-on. 
In case of EEPROM data failure, the previous stored setting cannot be recovered; so, when re-powered after 
a power mains interruption, unit restarts from standby mode 

 
 
 
 

Содержание ELLISSE HP

Страница 1: ...ELLISSE HP 1 Technical Specification ...

Страница 2: ...t decrease SW6 Unit switch ON OFF delay confirmation cancel L1 LCD with blue backlight L2 Standby mode LED red 2 1 Control Board Display D1 Tset Timer tens D2 Tset Timer units DP Decimal point S1 Time indicator S2 Temperature indicator S3 Delayed switch ON S4 Timer mode S5 Delayed switch OFF S6 Cooling mode S7 Dehumidification mode S8 Automatic mode S9 Sleep mode S10 Fan mode low fan speed S11 Med...

Страница 3: ...3 Remote control 3 1 Remote control display ...

Страница 4: ...n a speed feedback signal provided by the fan motor itself see the motor specs in enclosure 6 The target speed is compared to the feedback signal and the motor voltage is continuously adjusted in order to minimize the speed values difference Here are the details about the available fan speeds High FAN Med FAN Min FAN FAN MODE 1280 r min 5 1100 r min 5 920 r min 5 LCD symbols displayed In fan mode ...

Страница 5: ...urs The cooling defrosting subprogram which starts with Troom Tmin and finishes with Troom Tmin 2 C forces the compressor and ext fan and water disposal motor outputs to periodically switch OFF and switch ON for Tp_off minutes OFF state duration and Tp_on minutes ON state duration respectively When the defrosting function is active the internal fan speed must be set as follows Fan speed setting In...

Страница 6: ...rking cycle which is controlled as follows o ON continuously for Troom Tset 2 C o 6 minutes ON and 6 minutes OFF for Tset 2 C Troom Tset 2 C o 6 minutes ON and 12 minutes OFF for Tset 4 C Troom Tset 2 C o OFF continuously for Troom Tset 4 C Note After each dehumi mode start the compressor always waits 3 minutes before its first activation Regardless of Troom and Tset acquired compressor always run...

Страница 7: ...tched OFF Here are the details about the available fan speeds High FAN Med FAN Min FAN HEATING MODE 1280 r min 5 1100 r min 5 920 r min 5 When auto fan speed is selected only from the remote control by pressing B7 the actual speed is selected depending on room temperature and Tset as following only when the compressor is ON otherwise the int fan keeps OFF Tset 3 C Troom Tset minimum speed is enabl...

Страница 8: ...is placed in Stand by or when the power supply is disconnected in all these situations the function timer is reset and Tset restored to the last one received from remote controller In this status too all appliance s malfunctions are enabled 10 AUTOMATIC MODE This mode can be selected by pressing B2 or SW2 until the automatic symbol is shown on both the remote control s and L1 displays In this mode...

Страница 9: ...d L2 ON When the delay time set has elapsed the unit switches ON with latest selected settings All the timer symbols on both the remote controller and the local interface disappear 12 2 Timer OFF setting from remote control o With the unit in any working mode except standby press B9 to set the desired time delay from 1 to 12 hours after which the unit will switch OFF starting from timer confirmati...

Страница 10: ...unit will switch to standby mode L1 OFF and L2 ON o When the delay time set has elapsed the unit switches ON with previously selected settings All the timer symbols S2 S3 and S4 on the local interface disappear 12 4 Timer OFF setting from the display unit o With the unit in any working mode except standby press SW6 to set the desired time delay from 1 to 12 hours after which the unit will switch O...

Страница 11: ...by remote controller nor by display unit and the relative alarm code see table below is shown on display unit LCD Once the correct probe operation is restored the unit is placed in Standby mode 13 3 Internal fan alarm When fan speed feedback acquired keeps lower than 400 rpm for 20 seconds in all the working situation when the fan should operate the appliance stops to run all outputs are switched ...

Страница 12: ...y valve indoor fan max speed and outdoor fan work regardless Troom In Diagnostic mode all the alarms are enabled Defrost and Heatmax functions for Heating mode Defrost function for Cooling mode are enabled In Diagnostic mode by pressing the SW6 button the room temperature acquired by the probe is shown on D1 and D2 Press the standby key SW1 or disconnect the power supply to quit Diagnostic mode 15...

Страница 13: ...15 Wiring diagram ...

Страница 14: ...16 Sensor data ...

Страница 15: ......

Отзывы: