The heatmax subprogram starts when Troom 

 Theatmax and ends when 

Troom < Theatmax - 2°C, and forces the external fan to periodically switch 
OFF and switch ON for t_heatmax_off seconds (OFF state duration) and 
t_heatmax_on minutes (ON state duration) respectively. 
After switching the unit from heating to any other mode (including stand-by), the 4 way valve must remain 
energized until Rest_time seconds from previous compressor shut down have elapsed. 
In this mode too the compressor must be switched ON after a minimum Rest_time delay (180 sec) from last 
circuit power-on or from any former compressor shutdown. 
During this working mode all appliance’s malfunctions are enabled (see relative chapter below). 
 
9 SLEEP MODE 
This  mode  can  only  be  selected  from  the  remote  control  (by  pressing  B11)  and  can  only  be  used  in 
conjunction with cooling and heating modes. 
In cooling mode, as soon as sleep mode is enabled, the internal fan is forced to run at minimum speed and 
the  set  temperature  Tset  is  automatically  increased  by  1°C  after  1  hour  and  by  1°C  again  after  2  hours 
(starting from function activation or subsequent Tset modification). 
In heating mode, as soon as sleep mode is enabled, the internal fan is forced to run at minimum speed and 
the  set  temperature  Tset  is  automatically  decreased  by  2°C  after  1  hour  and  by  2°C  again  after  2  hours 
(starting from function activation or subsequent Tset modification). 
When sleep mode is disabled, when Tset is modified from the remote control, when the appliance is placed 
in Stand-by or when the power supply is disconnected, in all these situations the function timer is reset and 
Tset restored to the last one received from remote controller. 
In this status too all appliance’s malfunctions are enabled. 
 
10 AUTOMATIC MODE 
This mode can be selected by pressing B2 or SW2 until the automatic symbol is shown on both the remote 
control’s  and  L1  displays.  In  this  mode,  the  COOLING,  HEATING  and  FAN  functions  are  selected 
automatically depending on the continuously monitored room temperature value: 

o

 

If Troom < 17°C, the appliance works in heating mode, maximum speed enabled; 

o

 

If 17°C 

 Troom < 19°C, the appliance works in heating mode, medium speed enabled; 

o

 

If 19°C 

 Troom < 21°C, the appliance works in heating mode, minimum speed enabled; 

o

 

If 21°C 

 Troom 

 23°C, the appliance works in fan mode, minimum speed enabled; 

o

 

If 23°C < Troom 

 25°C, the appliance works in cooling mode, minimum speed enabled; 

o

 

If 25°C < Troom 

 27°C, the appliance works in cooling mode, medium speed enabled; 

o

 

If Troom > 27°C, the appliance works in cooling mode, maximum speed enabled. 

After  each  variation  the  int.  fan  speed  have  to  remain  constant  for  at  least  3  minutes  to  avoid  any 
inconvenient swings. For internal fan speed values refer to fan only, cooling and heating working mode. 
All the various subprograms and malfunctions enabled and described for each working mode before are still 
enabled in automatic mode too and have the same behavior previously defined. 
 
11 TURBO MODE 
This mode can only be selected from the remote control (by pressing B3) and switches the unit directly to 
cooling  mode  with  Tset=16°C  and  maximum  fan  speed.  Both  the  remote  control’s  and  L1  displays  are 
updated accordingly. 
 
 
 

Содержание ELLISSE HP

Страница 1: ...ELLISSE HP 1 Technical Specification ...

Страница 2: ...t decrease SW6 Unit switch ON OFF delay confirmation cancel L1 LCD with blue backlight L2 Standby mode LED red 2 1 Control Board Display D1 Tset Timer tens D2 Tset Timer units DP Decimal point S1 Time indicator S2 Temperature indicator S3 Delayed switch ON S4 Timer mode S5 Delayed switch OFF S6 Cooling mode S7 Dehumidification mode S8 Automatic mode S9 Sleep mode S10 Fan mode low fan speed S11 Med...

Страница 3: ...3 Remote control 3 1 Remote control display ...

Страница 4: ...n a speed feedback signal provided by the fan motor itself see the motor specs in enclosure 6 The target speed is compared to the feedback signal and the motor voltage is continuously adjusted in order to minimize the speed values difference Here are the details about the available fan speeds High FAN Med FAN Min FAN FAN MODE 1280 r min 5 1100 r min 5 920 r min 5 LCD symbols displayed In fan mode ...

Страница 5: ...urs The cooling defrosting subprogram which starts with Troom Tmin and finishes with Troom Tmin 2 C forces the compressor and ext fan and water disposal motor outputs to periodically switch OFF and switch ON for Tp_off minutes OFF state duration and Tp_on minutes ON state duration respectively When the defrosting function is active the internal fan speed must be set as follows Fan speed setting In...

Страница 6: ...rking cycle which is controlled as follows o ON continuously for Troom Tset 2 C o 6 minutes ON and 6 minutes OFF for Tset 2 C Troom Tset 2 C o 6 minutes ON and 12 minutes OFF for Tset 4 C Troom Tset 2 C o OFF continuously for Troom Tset 4 C Note After each dehumi mode start the compressor always waits 3 minutes before its first activation Regardless of Troom and Tset acquired compressor always run...

Страница 7: ...tched OFF Here are the details about the available fan speeds High FAN Med FAN Min FAN HEATING MODE 1280 r min 5 1100 r min 5 920 r min 5 When auto fan speed is selected only from the remote control by pressing B7 the actual speed is selected depending on room temperature and Tset as following only when the compressor is ON otherwise the int fan keeps OFF Tset 3 C Troom Tset minimum speed is enabl...

Страница 8: ...is placed in Stand by or when the power supply is disconnected in all these situations the function timer is reset and Tset restored to the last one received from remote controller In this status too all appliance s malfunctions are enabled 10 AUTOMATIC MODE This mode can be selected by pressing B2 or SW2 until the automatic symbol is shown on both the remote control s and L1 displays In this mode...

Страница 9: ...d L2 ON When the delay time set has elapsed the unit switches ON with latest selected settings All the timer symbols on both the remote controller and the local interface disappear 12 2 Timer OFF setting from remote control o With the unit in any working mode except standby press B9 to set the desired time delay from 1 to 12 hours after which the unit will switch OFF starting from timer confirmati...

Страница 10: ...unit will switch to standby mode L1 OFF and L2 ON o When the delay time set has elapsed the unit switches ON with previously selected settings All the timer symbols S2 S3 and S4 on the local interface disappear 12 4 Timer OFF setting from the display unit o With the unit in any working mode except standby press SW6 to set the desired time delay from 1 to 12 hours after which the unit will switch O...

Страница 11: ...by remote controller nor by display unit and the relative alarm code see table below is shown on display unit LCD Once the correct probe operation is restored the unit is placed in Standby mode 13 3 Internal fan alarm When fan speed feedback acquired keeps lower than 400 rpm for 20 seconds in all the working situation when the fan should operate the appliance stops to run all outputs are switched ...

Страница 12: ...y valve indoor fan max speed and outdoor fan work regardless Troom In Diagnostic mode all the alarms are enabled Defrost and Heatmax functions for Heating mode Defrost function for Cooling mode are enabled In Diagnostic mode by pressing the SW6 button the room temperature acquired by the probe is shown on D1 and D2 Press the standby key SW1 or disconnect the power supply to quit Diagnostic mode 15...

Страница 13: ...15 Wiring diagram ...

Страница 14: ...16 Sensor data ...

Страница 15: ......

Отзывы: