The heatmax subprogram starts when Troom
≥
Theatmax and ends when
Troom < Theatmax - 2°C, and forces the external fan to periodically switch
OFF and switch ON for t_heatmax_off seconds (OFF state duration) and
t_heatmax_on minutes (ON state duration) respectively.
After switching the unit from heating to any other mode (including stand-by), the 4 way valve must remain
energized until Rest_time seconds from previous compressor shut down have elapsed.
In this mode too the compressor must be switched ON after a minimum Rest_time delay (180 sec) from last
circuit power-on or from any former compressor shutdown.
During this working mode all appliance’s malfunctions are enabled (see relative chapter below).
9 SLEEP MODE
This mode can only be selected from the remote control (by pressing B11) and can only be used in
conjunction with cooling and heating modes.
In cooling mode, as soon as sleep mode is enabled, the internal fan is forced to run at minimum speed and
the set temperature Tset is automatically increased by 1°C after 1 hour and by 1°C again after 2 hours
(starting from function activation or subsequent Tset modification).
In heating mode, as soon as sleep mode is enabled, the internal fan is forced to run at minimum speed and
the set temperature Tset is automatically decreased by 2°C after 1 hour and by 2°C again after 2 hours
(starting from function activation or subsequent Tset modification).
When sleep mode is disabled, when Tset is modified from the remote control, when the appliance is placed
in Stand-by or when the power supply is disconnected, in all these situations the function timer is reset and
Tset restored to the last one received from remote controller.
In this status too all appliance’s malfunctions are enabled.
10 AUTOMATIC MODE
This mode can be selected by pressing B2 or SW2 until the automatic symbol is shown on both the remote
control’s and L1 displays. In this mode, the COOLING, HEATING and FAN functions are selected
automatically depending on the continuously monitored room temperature value:
o
If Troom < 17°C, the appliance works in heating mode, maximum speed enabled;
o
If 17°C
≤
Troom < 19°C, the appliance works in heating mode, medium speed enabled;
o
If 19°C
≤
Troom < 21°C, the appliance works in heating mode, minimum speed enabled;
o
If 21°C
≤
Troom
≤
23°C, the appliance works in fan mode, minimum speed enabled;
o
If 23°C < Troom
≤
25°C, the appliance works in cooling mode, minimum speed enabled;
o
If 25°C < Troom
≤
27°C, the appliance works in cooling mode, medium speed enabled;
o
If Troom > 27°C, the appliance works in cooling mode, maximum speed enabled.
After each variation the int. fan speed have to remain constant for at least 3 minutes to avoid any
inconvenient swings. For internal fan speed values refer to fan only, cooling and heating working mode.
All the various subprograms and malfunctions enabled and described for each working mode before are still
enabled in automatic mode too and have the same behavior previously defined.
11 TURBO MODE
This mode can only be selected from the remote control (by pressing B3) and switches the unit directly to
cooling mode with Tset=16°C and maximum fan speed. Both the remote control’s and L1 displays are
updated accordingly.