A
fan
B
cooling radiator
C
filter
D
circulation pump
E
regulating valve
F
non-return valve
G
ground circuit return line
H
shut-off valves
For more detailed information in connecting to an air conditioner,
refer to the manufacturer’s instructions.
2.5. Electrical connections
A general description of the needed electrical connections is given in this section. The
actual connections should be made according to the wiring diagrams delivered with the
heat pump.
Do not connect devices that draw over 2 A of current directly to
the controller. Use a contactor instead.
Feed cables
Model
Cable size
RE 35
5 x 10 mm
2
RE 42
5 x 10 mm
2
RE 55
4 x 16 mm
2
+ 16 mm
2
RE 70
4 x 16 mm
2
+ 16 mm
2
RE 85
4 x 25 mm
2
+ 16 mm
2
Содержание RE 35
Страница 2: ......
Страница 58: ...56 67 RE01 1445EN Wilo Stratos Para 25 1 12 WSP01 ver 1...
Страница 59: ...RE01 1445EN 57 67 Wilo Stratos 40 1 12 WSP02a ver 1 WSP02b ver 1...
Страница 60: ...58 67 RE01 1445EN Wilo IPL 40 115 0 55 2 WIPL03 ver 1...
Страница 61: ...RE01 1445EN 59 67 Wilo IPL 50 115 0 75 2 WIPL02 ver 1...
Страница 62: ...60 67 RE01 1445EN Wilo IPL 50 120 1 5 2 and Wilo IPL 50 130 2 2 2 WIPL01 ver 1...
Страница 63: ...RE01 1445EN 61 67 Wilo Stratos Para 25 1 7 WSP03 ver 1...
Страница 70: ...68 67 RE01 1445EN...
Страница 71: ......
Страница 72: ...Tarmontie 4 FI 15860 HOLLOLA FINLAND Tel 358 3 85 761 Fax 358 3 857 6239 Email info oilon com www oilon com...