FlueGasTempSens
MaxTempFlGasGas
MaxTempFlGasOil
4.31 Activating O
2
trim control (WD200)
At the end of commissioning activate O
2
trim control from the display and operation unit
menu.
Operation
O2Ctrl activate
deactivated
activated
4.32 Backing up parameters
1. Start backing up parameters by selecting the following from the display and
operating unit:
Updating
ParamBackup
BackupInfo
LMV5x –> AZL
AZL –> LMV5x
2. Start backing up by pressing
Enter
.
3. Parameter backup is done when the text
Parameters saved
appears on the display.
M4219 2305EN
75 (111)