![Oilon GP-600 M Скачать руководство пользователя страница 58](http://html1.mh-extra.com/html/oilon/gp-600-m/gp-600-m_operation-and-maintenance-manual_4505353058.webp)
Press
Enter
at the desired parameter.
Curve point 6 ver. 4
Change setting using the
Select -/+
buttons. Then servomotors drive to their new
position. During that time, the display shows “>” instead of “:”. Confirm the change by
pressing
Enter
or undo by pressing
Esc
. Then you return to the previous menu level.
The servomotor turning angle is 0–90° and setting accuracy 0.1°. The capacity and
variable speed drive setting range is 0–100% and they can be set at 0.1 % accuracy.
Adjust at point 1:
● burner minimum load, note ratio
● set fan rotation speed as small as possible, but not under 60%
● check combustion values with flue gas analysis
● check the combustion flame
● set load value and point load is determined according to current fuel consumption
as a percentage of maximum load
In the settings for air servomotors and variable speed drive control, residual oxygen is
adjusted as desired for each curve point.
When you have made changes, press
Esc
.
Curve point 7 ver. 4
If you want to save the changes to curve point settings, press
Enter
. If you want to
leave without saving changes, press
Esc
. After this, you will return to the point where
you can scroll through curve points. Return to the menu by pressing
Esc
.
Creating curve point manually by changing load
1. At the menu level
CurveSetting
, move the pointer to
Manually
.
Curve point 8 ver. 4
2. Press
Enter
, and use the
Select -/+
buttons to increase or decrease burner start
capacity.
56 (111)
M4219 2305EN
Содержание GP-600 M
Страница 2: ......
Страница 16: ...Block diagram of contact links Block diagram ver 7 14 111 M4219 2305EN...
Страница 87: ...5 5 Time sequence diagram gas use 7550f57e 0515 Gp1 ver 6 M4219 2305EN 85 111...
Страница 113: ...M4219 2305EN 111 111...
Страница 114: ...112 111 M4219 2305EN...
Страница 115: ......