Burner
Factory setting "W.C.
300 M-II
12.5
400 M-I – 600 M
16.1
700 M - 700 M-III
20.1
When using variable speed drive
● factory setting is set to 4.01 "W.C.
● maximum adjustment range should be between 35 Hz and 50 Hz
To ensure proper burner function, the differential air pressure switch
may have to be readjusted to match the actual conditions at the
installation site. Make sure not to exceed the given CO limit.
To adjust differential air pressure switch setting at current nominal burner
capacity
1. Remove the screws and open the protective cover.
2. Start the burner.
3. Turn the switch slowly towards the maximum until the burner shuts down.
4. Turn the switch approx. 2.0 "W.C. from this point backwards (towards the
minimum).
5. Attach the protective cover and reset.
4.5 Adjusting gas pressure switch
Gas pressure switch, max.
1 Adjusting scale
2 Reset, gas pressure switch, max.
3 Pressure measuring connection
A416M ver. 3
Gas pressure switch max. should cause a permanent interlocking if burner capacity
increases to be more than 1.15 times the nominal value, or if the pressure exceeds
more than 1.3 times the nominal pressure.
M4219 2305EN
37 (111)