![Oilon GP-600 M Скачать руководство пользователя страница 21](http://html1.mh-extra.com/html/oilon/gp-600-m/gp-600-m_operation-and-maintenance-manual_4505353021.webp)
Installation, commissioning, or service of the appliance is to be carried
out by authorized and trained personnel only, adhering to all local
regulations and requirements.
Space requirements ver. 1
Legend
Minimum
dimension, ft
a
(left)
2.6
b
(front)
3.6
c
(right)
2.6
d
(top)
3.3
It is recommended to leave more space around the burner. These are only the
minimum requirements.
3.3 Installing burner
● Prepare boiler front plate in accordance with the given dimensions.
● Coat bolt threads with graphite-bearing grease prior to fitting.
● Install burner so that motor shaft lies horizontally. It is not allowed to install burner
upside down.
● Remove transportation bracket after burner is attached to boiler.
● Make sure there is enough free space on the side to allow burner to swing fully
open.
Install the burner firmly. Vibration may cause damage to the burner or its
components.