4.15 Setting ratio curve
Curve points
There can be 15 curve points at the maximum.
Set curve points in the following menu level:
Params. & Display
RatioControl
GasSettings
CurveSettings
Point
Manual
Creating curve point individually
Current servomotor positions in degrees, variable speed drive control and capacity in
percentages are shown on the right side of the display, starting from the top corner. The
pointer is positioned at
Point
.
Curve point 1 ver. 4
Press
Enter
to scroll through stored curve points.
Curve point 2 ver. 4
The pointer is positioned at the colon below the text
Point
. The running number of the
stored curve point is shown after the colon.
Curve points are stored according to capacity from smallest to biggest. Curve points
can be added at any order. Scroll through curve points using the
Select -/+
buttons.
The setting for an unused curve point is
XXXX
and its running number is one number
greater than that of the last stored curve point.
54 (111)
M4219 2305EN