3.5 Burner hinges
Swinging the burner open ver. 4
As standard, the burner swings to the left. Right side hinging is delivered on request
only.
Switch off electric power from the burner before swinging the burner
open.
3.6 Installing burner to gas supply line
Supply line
If necessary, decrease the supply gas pressure with pressure regulating assembly. The
gas supply line after the pressure regulator must be of the same size or one size larger
than the valve train size.
As standard, the gas connection to the burner is from the right side. The valves shown
in the following example may vary from those delivered.
B352U ver. 3
M4219 2305EN
23 (111)