Effective 11/2010
V
Air Changes by Room Size/Machine Size
Air Changes Required in a Room Per Hour for All Models
Model Number
Room Volume in Cubic Feet (ft
3
)
1000 2000 3000 4000 5000 6000 7000
8000 9000 10000 12500
OG-15
5
2.5
2
1.5
1
1
1
1
1
1
1
OG-20
8
4
2.5
2
2
1.5
1
1
1
1
1
OGS-20
8
4
2.5
2
2
1.5
1
1
1
1
1
OG-25
10
5
4
2.5
2.5
2
1.5
1
1
1
1
OG-50
20
10
7.5
5
5
4
3
2.5
2
2
1.5
OG-100
NR
20
15
10
9
8
7
5
4
4
3
OG-175
NR
25
18
12.5
11
10
8
6
5
5
4
OG-250
NR
30
22.5
15
13
11
9
7.5
7
6
5
OG-375
NR
NR
30
27
22.5
18
15
13
11
8
7
OG-500
NR
NR
NR
30
27
22.5
18
15
13
11
8
OG-650
NR
NR
NR
NR
30
27
22.5
18
15
13
11
OG-750
NR
NR
NR
NR
NR
30
27
22.5
18
16
13
OG-1000
NR
NR
NR
NR
NR
NR
NR
30
26
22
17
OG-1250
NR
NR
NR
NR
NR
NR
NR
NR
NR
30
24
OG-1500
NR
NR
NR
NR
NR
NR
NR
NR
NR
NR
30
CFP-15+/15M
5
2.5
2
1.5
1
1
1
1
1
1
1
MOGS-100
NR
20
15
10
9
8
7
5
4
4
3
Notes:
1.
NR
means that the models indicated are not recommended for rooms of this size.
2.
For air changes requirements for models
OG-2000
and above, please contact
OGSI
.
Содержание MOGS - 100
Страница 2: ......
Страница 6: ......
Страница 50: ...Effective 11 2010 44 MOGS 100 Filling Manifold Design Installation Optional...
Страница 58: ......
Страница 59: ...Appendix...
Страница 60: ......
Страница 67: ...Effective 11 2010 VII Maintenance Log Date Part Reason for Maintenance Authorized Service Technician Signature...