22
SP2+O2HY
SP2
ON
OFF
OUT2 Action
PV
Time
Time
Figure 3.4 Output 2 Process
Low Alarm
Figure 3.4 Output 2 Process
Low Alarm
3-4 Alarm
3-4 Alarm
Output 2 can be selected as an alarm output. There are 6 types of alarm functions and one dwell timer that can be
selected. Four seperate alarm modes (ALMD) can additionally be applied to each alarm function.
A
sets two absolute trigger
levels. When the process is higher than
SP2, a process high alarm
occurs,
and the alarm is off as the process is lower
than SP2-O2HY. When the process is lower
than SP2, a process low alarm
occurs and the alarm is off as the process
is higher than SP2+O2HY. A process alarm
is independent of set point.
process alarm
(PV.HI)
( PV.LO )
A
sets two absolute trigger
levels. When the process is higher than
SP2, a process high alarm
occurs,
and the alarm is off as the process is lower
than SP2-O2HY. When the process is lower
than SP2, a process low alarm
occurs and the alarm is off as the process
is higher than SP2+O2HY. A process alarm
is independent of set point.
process alarm
(PV.HI)
( PV.LO )
A
alerts the user when the
process deviates too far from set point.
When the process is higher than SV+SP2, a
deviation high alarm
occurs and the
alarm is off as the process is lower than
SV+SP2-O2HY. When the process is lower
than SV+SP2, a deviation low alarm
occurs and the alarm is off as the process
is higher than SV+SP2+O2HY. Trigger level
of deviation alarm is moving with set point.
deviation alarm
(DE.HI)
(DE.LO)
A
alerts the user when the
process deviates too far from set point.
When the process is higher than SV+SP2, a
deviation high alarm
occurs and the
alarm is off as the process is lower than
SV+SP2-O2HY. When the process is lower
than SV+SP2, a deviation low alarm
occurs and the alarm is off as the process
is higher than SV+SP2+O2HY. Trigger level
of deviation alarm is moving with set point.
deviation alarm
(DE.HI)
(DE.LO)
A
presets two trigger levels relative to the set point. The two trigger levels are
and
for alarm. When the process is higher than ( SV+SP2 ) or lower than ( SV - SP2 ), a deviation band high
alarm
occurs. When the process is within the trigger levels, a deviation band low alarm
occurs.
deviation band alarm
SV+SP2
SV - SP2
(DB.HI)
(DB.LO)
A
presets two trigger levels relative to the set point. The two trigger levels are
and
for alarm. When the process is higher than ( SV+SP2 ) or lower than ( SV - SP2 ), a deviation band high
alarm
occurs. When the process is within the trigger levels, a deviation band low alarm
occurs.
deviation band alarm
SV+SP2
SV - SP2
(DB.HI)
(DB.LO)
Normal Alarm : ALMD = NORM
When a normal alarm is selected, the alarm output is de-energized in the non-alarm condition and energized in
an alarm condition.
Normal Alarm : ALMD = NORM
When a normal alarm is selected, the alarm output is de-energized in the non-alarm condition and energized in
an alarm condition.
Note: In the above descriptions;
denotes the current set point value for control which is different from SP1 as the
ramp function is performed.
SV
Note: In the above descriptions;
denotes the current set point value for control which is different from SP1 as the
ramp function is performed.
SV
Latching Alarm : ALMD = LTCH
If a latching alarm is selected, once the alarm output is energized, it will remain unchanged even if the alarm
condition is cleared. The latching alarm is reset when the RESET key is pressed, once the alarm condition is
removed.
Latching Alarm : ALMD = LTCH
If a latching alarm is selected, once the alarm output is energized, it will remain unchanged even if the alarm
condition is cleared. The latching alarm is reset when the RESET key is pressed, once the alarm condition is
removed.
Holding Alarm : ALMD = HOLD
A holding alarm prevents or inhibits an alarm from kicking on during initial controller power up. The alarm is enabled
only when the process reaches the set point
Holding Alarm : ALMD = HOLD
Latching / Holding Alarm : ALMD = LT.HO
A latching / holding alarm performs both holding and latching function. The latching alarm is reset when the RESET
key is pressed, once the alarm condition is removed.
Latching / Holding Alarm : ALMD = LT.HO
Alarm Failure Transfer
failure mode
ON
O2FT
OFF
O2FT
is activated as the unit enters
. Alarm will go on if
is set for
and go off if
is set for
. The unit will enter failure mode when a sensor break occurs or if the A-D converter of the unit fails.
Alarm Failure Transfer
failure mode
ON
O2FT
OFF
O2FT
Figure 3.3 Output 2 Deviation
High Alarm
Figure 3.3 Output 2 Deviation
High Alarm
SV+SP2
SV+SP2-O2HY
ON
OFF
OUT2 Action
PV
Time
Time
ALARM FUNCTIONS:
ALARM MODES: