1-6 Parameter Descriptions
1-6 Parameter Descriptions
Parameter
Notation
Default
Value
Select parameters to be locked
3
: All data is locked
LOCK
0
Parameter Description
2
: T type T/C
3
: E type T/C
4
: B type T/C
5
: R type T/C
6
: S type T/C
1
: K type T/C
7
N typeT/C
:
8
L type T/C
:
9
PT 100 ohms DIN
:
10
PT 100 ohms JIS
:
11
4 - 20 mA
:
12
0 - 20 mA
:
14
0 - 1V
:
13
: 0 - 60 mV
INPT
Input sensor selection
1
(0)
SP2
Set point for output 2 when
output 2 performs alarm
function or dwell timer
Low: -19999
High :45536
18.0°
(
)
F
10.0 °C
SP1
Set point for output 1
Low: SP1L
High :SP1H
77.0 °
(
)
F
25.0 °C
15
0 - 5V
:
16
1 - 5V
:
17
0 - 10V
:
2
: Setup and User data is locked
Set point is un- locked
1
: Setup data is locked
0
: No parameters are locked
:
0
J type T/C
Range
UNIT
Input unit selection
0
: Degree C unit
1
: Degree F unit
2
: Process unit
0
(1)
DP
Decimal point selection
1
0
: No decimal point
1
: 1 decimal digit
2
: 2 decimal digits
3
: 3 decimal digits
INLO
INHI
Input low scale value
Input high scale value
-19999
INLO+50
45486
45536
Low:
Low:
High:
High:
0°
(
)
F
-17.8 °C
200.0°
(
)
F
93.3 °C
SP1L
Low limit of set point
value
-19999
High:
0°
(
)
F
-17.8 °C
45536
Low:
SHIF
PV shift (offset) value
(-200.0
)
-360.0 °C
°C
0.0
Low:
360.0 °F
( 200.0 °C)
High:
FILT
Filter damping time
constant of PV
(seconds)
2
: 0.5
4
: 2
5
: 5
6
: 10
7
: 20
8
: 30
9
: 60
0
: 0
1
: 0.2
3
: 1
2
SP1H
High limit of set point
value
SP1L
High:
1000°
(
)
F
537.8 °C
45536
Low:
PB
Proportional band value
18.0
(
)
°F
10.0 °C
Low: 0
932.0 °F
(500.0 °C)
High:
TI
TD
Integral time value
Derivative time value
100
25.0
Low: 0
Low: 0
1000 sec
360.0 sec
High:
High:
DISP
Normal display selection
: Display process value
0
: Display set point 1 value
1
0
10