nVent.com
|
39
8.
Supplement
8.1 Technical Data
Thermocouple input
Designation
Measuring
range
1
Measuring
accuracy
2
Ambient
temperature
coefficient
EN
Fe-CuNi “L”
-200… +900 °C ≤ 0.25%
100 ppm/ K
Fe-CuNi “J”
60584
-200…+1200 °C ≤ 0.25%
100 ppm/ K
Cu-CuNi “U”
-200… +600 °C ≤ 0.25%
100 ppm/ K
Cu-CuNi “T”
60584
-200… +400 °C ≤ 0.25%
100 ppm/ K
NiCr-Ni “K”
60584
-200…+1372 °C ≤ 0.25%
100 ppm/ K
NiCr-CuNi “E”
60584
-200… +900 °C ≤ 0.25%
100 ppm/ K
NiCrSi-NiSi “N”
60584
-100…+1300 °C ≤ 0.25%
100 ppm/ K
Pt10Rh-Pt “S”
60584
0… +1768 °C
≤ 0.25%
100 ppm/ K
Pt13Rh-Pt “R”
60584
0… +1768 °C
≤ 0.25%
100 ppm/ K
Pt30Rh-Pt6Rh “B” 60584
0… +1820 °C
≤ 0.25%
3
100 ppm/ K
W5Re-W26Re “C”
0… +2320 °C
≤ 0.25%
100 ppm/ K
W3Re-W25Re “D”
0… +2495 °C
≤ 0.25%
100 ppm/ K
W3Re-W26Re
0… +2400 °C
≤ 0.25%
100 ppm/ K
Cold junction: Pt100 internal
1
The specifications refer to an ambient temperature of 20 °C.
2
Incl. measuring accuracy at the cold junction. The accuracy values refer to the
maximum measuring range. Small measuring ranges lead to reduced linearisation
accuracy.
3
In the range of 300 ... 1820 °C