30
|
nVent.com
Parameters
Value /
Selection
Description
Set time t2
t2
(Timer follow-
up time)
-1…
0…
+9999
This time (in seconds) can be used to
transmit a time limited or acknowledgeable
signal after the timer time has elapsed.
0 = switched off
1…9999 = active for the set time
-1 = active until acknowledged
Acknowledgement:
For t2 = -1 the timer follow-up time is
infinite. Cancel the signal using a function
key or the binary signal.
Tolerance band
toLt
0
…9999
The set timer time only elapses when the
process value has reached the tolerance
band.
0 = Start without tolerance band
The tolerance band (in Kelvin) is
symmetrical in relation to the SP set point
value.
(1)
w/x
t
SP
t1
toLt
(1) = Start via function key, binary input or
when power ON
7.6 Outputs
The configuration of the device outputs is subdivided in binary
outputs (OutL) and analog outputs (OutA). Binary outputs are
relays and logic outputs. The switching states of the binary
outputs 1 to 4 are shown in the display (K1 to K4).
Binary outputs
Output 1 (Out1) = Relay
Output 2 (Out2) = Relay
Output 3 (Out3) = Logic output Output 4 (Out4) = Relay (option)