1.5 Type-dependent factory settings
The following tables show the type-dependent factory settings.
The standard factory settings are shown in the respective
sections of this manual.
The settings for type TCONTROL-CONT-03 are also valid for type
TCONTROL-CONT-03/COM.
The settings for type TCONTROL-CONT-03/MA are also valid for
type TCONTROL-CONT-03/COMA.
Set points (available within User level - USEr)
Parameter
Factory setting for type
TCONTROL- CONT-03
TCONTROL- CONT-03/MA
Set point 1 (SP1)
5.0
5.0
Set point 2 (SP2)
0.0
0.0
Parameter level (PArA)
Parameter
Factory setting for type
TCONTROL- CONT-03
TCONTROL- CONT-03/MA
Proportional
band (Pb1)
0.0
10.0
Derivative time (dt)
0 s
80 s
Reset time (rt)
0 s
350 s
Configuration level (ConF)
Parameter
Factory setting for type
TCONTROL- CONT-03
TCONTROL- CONT-03/MA
Analog input (InP):
Scale low level (SCL) -50
-50
Scale high level
(SCH)
250
250
Controller (Cntr):
Controller type
(CtYP)
1 (= 2-state ON/OFF)
4 (= continuous
4…20 mA)
Output value at
Out of Range
100
100
Manual mode
inhibited
inhibited
Self-optimization
inhibited
inhibited
1