background image

Содержание 1244-0006829

Страница 1: ...TCONTROL CONT 03 COMPACT MICROPROCESSOR CONTROLLER OPERATING AND INSTALLATION MANUAL...

Страница 2: ......

Страница 3: ...4 1 Display and operating elements 12 4 2 Level concept 12 4 3 User level configuration 13 4 4 Defining various user levels 14 4 5 Entries and operator prompting 14 4 6 Controller 15 4 7 Display of th...

Страница 4: ...u encounter problems The manual is valid from device software version 223 01 04 Chapter 4 7 Display of the software version Warning signs DANGER This symbol indicates that Injury or death caused by el...

Страница 5: ...702071 9 1134 23 53 nVent Part No 1244 0006981 TCONTROL CONT 03 COMA nominal dimension 48 mm x 48 mm 1 analog input 2 relays 1 analog output user configurable 0 4 20 mA or 0 2 10 V Interface RS485 1...

Страница 6: ...ROL CONT 03 MA Set point 1 SP1 5 0 5 0 Set point 2 SP2 0 0 0 0 Parameter level PArA Parameter Factory setting for type TCONTROL CONT 03 TCONTROL CONT 03 MA Proportional band Pb1 0 0 10 0 Derivative ti...

Страница 7: ...Binary outputs OutL Binary output 1 Out1 1 Controller output 1 5 Limit comparator 1 Binary output 2 Out2 5 Limit comparator 1 6 Limit comparator 2 Binary output 3 Out3 0 no function 0 no function Bina...

Страница 8: ...alue AL2 4 Mains ON delay Power ON delay Strt Mains ON delay Power ON delay Strt 5 Analog input Probe type Sensor type InP Analog input Probe type Sensor type InP 6 Display Decimal point dEC Display D...

Страница 9: ...s a limited resistance to organic solvents e g methylated spirits white spirit etc Do not use abrasive or high pressure cleaning equipment 2 2 Dimensions Close mounting Minimum spacing of panel cut ou...

Страница 10: ...ontacts becoming welded in the event of a short circuit occurring at that point The electromagnetic compatibility conforms to the standards and regulations cited in the technical data Run input output...

Страница 11: ...t 1 K1 Relay 230 V AC 3 A 2 Output 2 K2 Relay 230 V AC 3 A 3 Output 3 K3 Logic 0 14 V alternative to binary input 1 configurable 4 Output 4 K4 option Analog output or Relay 230 V AC 3 A 5 1 Binary inp...

Страница 12: ...uction previous parameter Value increase next parameter 5 Signals green LED Manual mode active Ramp function active Timer active 4 2 Level concept The parameters for the device setting are structured...

Страница 13: ...3 User level configuration A maximum of eight frequently used parameters can be made available in the User level Use the Setup program to configure these parameters Once these parameters are selected...

Страница 14: ...nfiguration level can also be inhibited via the binary function Chapter 7 7 Binary functions 4 5 Entries and operator prompting Entering values When entries are made within the levels the parameter sy...

Страница 15: ...er the entry with or automatic return after 2 s or cancel the entry with the value will not be applied 4 6 Controller Increase set point value Reduce set point value Normal display Regulation to set p...

Страница 16: ...manual mode in the event of overrange underrange and probe break Manual mode exit 1 Exit the manual mode using function key 2 s Operation via binary functions Further operating possibilities for the...

Страница 17: ...and timer is not running Chapter 7 5 Timer tL Timer running time only if timer runs Chapter 7 5 Timer tr Residual timer running time only if timer runs Chapter 7 5 Timer OC Service counter display on...

Страница 18: ...a switching output the cycle time should be selected such that on one hand no inadmissible process values fluctuations are generated and on the other hand no overload of the actuators occurs by the c...

Страница 19: ...the parameter This means for example that interface parameters can only be configured if the device is equipped with an interface TIP Some parameters can only be programmed through the Setup program I...

Страница 20: ...Analog input 2 Process value 3 Current set point value 4 Ramp limit value 5 Ramp set point value 6 Reserved 7 Reserved 8 Set point value 1 9 Set point value 2 10 Controller output value 100 100 11 Con...

Страница 21: ...nS 0 Pt100 3 wire 1 Pt1000 3 wire 2 Pt100 2 wire 3 Pt1000 2 wire 4 KTY 2 wire 5 9 reserved 10 Cu CuNi T 11 Fe CuNi J 12 Cu CuNi U 13 Fe CuNi L 14 NiCr Ni K 15 Pt10Rh Pt S 16 Pt13Rh Pt R 17 Pt30Rh Pt6R...

Страница 22: ...er off 63 of the alterations are acquired after 2x filter time constant 2nd order filter at a step change When the filter time constant is large High damping of interference signals Slow reaction of t...

Страница 23: ...oint value w e g heating 2 Direct Output value Y of the controller is 0 if process value x is higher than set point value w e g cooling Output value manual mode HAnd 100 101 Defines the output value a...

Страница 24: ...e manual mode using the keys or the binary input Setting in the Setup program Controller Manual mode Self optimization Setup free inhibited If self optimization is inhibited it cannot be started using...

Страница 25: ...of ramp rate for functions 1 to 3 only Tolerance band toLP 0 9999 Range of the tolerance band in Kelvin around the set point value 0 Tolerance band inactive for functions 1 to 3 only For the ramp fun...

Страница 26: ...e ouput or an internal function can be initiated There are 2 limit comparators available LC1 LC2 The switching differential HySt can be user defined and will always be symmetrical in relation to the a...

Страница 27: ...lk8 alarm value AL Alarm value range for lk1 and lk2 0 9999 Hysteresis HySt 0 1 9999 Hysteresis in respect to the alarm value see limit comparator functions lk1 lk8 hysteresis HySt Response by Out of...

Страница 28: ...signal Subsequently the timer time t1 is counted to zero either immediately or after the process value has reached a programmable tolerance limit The timer can be stopped waiting time or cancelled How...

Страница 29: ...ection Description Function FnCt 0 1 2 no function Timer Timer for time delayed control Start condition Strt 0 1 2 Manual start by using the function key or the binary signal no restart or continuatio...

Страница 30: ...0 9999 The set timer time only elapses when the process value has reached the tolerance band 0 Start without tolerance band The tolerance band in Kelvin is symmetrical in relation to the SP set point...

Страница 31: ...Timer runs Timer completed Timer waiting reserved reserved Tolerance band signal ramp Ramp end signal Service alarm reserved Actuate the F key Manual mode Analog output The device can optionally be e...

Страница 32: ...be used to put out the process value value range 150 500 C this means 150 500 C 0 20 mA Zero point 150 End value 500 End value End 1999 100 9999 7 7 Binary functions In terms of this manual a functio...

Страница 33: ...self optimization Abort self optimization Change to manual mode Controller off controller outputs are switched off Switch on controller Inhibit manual mode Stop ramp Abort ramp Restart ramp Set point...

Страница 34: ...r display only effective after the timer is started no function Display of residual timer time Display of timer run time Time out tout 0 180 255 Time period in seconds after which the device automatic...

Страница 35: ...conds in the normal display Change to manual mode Starting the timer Timer abort Stop timer continue timer run Timer start abort Display timer value manual Level inhibit Setup None ConF PArA and ConF...

Страница 36: ...y hour in the EEPROM the counter value saved last is used to continue counting after a power failure Special features on the device when selecting Number operation and display only in the User level V...

Страница 37: ...imer signal Timer runs Timer completed Timer waiting Tolerance band signal Ramp end Service alarm Key actuation Manual mode User level Setup A maximum of eight parameters from the various levels can b...

Страница 38: ...data bits 1 stop bit even parity 8 data bits 2 stop bits no parity Device address Adr 0 1 255 Address in data network Min response time Setup 0 500 ms Time period in milli seconds that elapses between...

Страница 39: ...0 ppm K NiCrSi NiSi N 60584 100 1300 C 0 25 100 ppm K Pt10Rh Pt S 60584 0 1768 C 0 25 100 ppm K Pt13Rh Pt R 60584 0 1768 C 0 25 100 ppm K Pt30Rh Pt6Rh B 60584 0 1820 C 0 25 3 100 ppm K W5Re W26Re C 0...

Страница 40: ...ring current approx 250 A Lead compensation Not required for three wire circuit For a 2 wire circuit the lead resistance can be compensated by correcting the actual value 1 The accuracy values refer t...

Страница 41: ...ce thermometer Voltage 2 10 V 0 10 V Current 4 20 mA 0 20 mA detected not detected only overranges are detected Outputs Relay N O Contact rating Contact life max 3 A at 230 V AC resistive load 150 000...

Страница 42: ...pollution degree 2 Amperage max 15 VA Data backup EEPROM Electrical connection at the back via screw terminals Conductor cross section up to max 1 3 mm2 Installation information on conductor cross sec...

Страница 43: ...e measure intended for this case 1999 flashing Underrange for the value being displayed Is the medium being measured within the range too hot too cold Check probe for break and probe short circuit Che...

Страница 44: ...ation SO Prerequisites The following prerequisites must be fulfilled to be able to start self optimization No active level inhibit via binary functions binF No active inhibit of Parameter level via Se...

Страница 45: ...alue End 100 For modulating controllers only Determine the actuator time tt and set in the Parameter level Start of self optimization 1 Simultaneously press the keys 2 s In the lower display tUnE appe...

Страница 46: ...46 nVent com...

Страница 47: ...nVent com 47...

Страница 48: ...nvent com Italia Tel 39 02 577 61 51 Fax 39 02 577 61 55 28 salesit nvent com Lietuva Latvija Eesti Tel 370 5 2136633 Fax 370 5 2330084 info baltic nvent com Magyarorsz g Tel 36 1 253 7617 Fax 36 1 2...

Отзывы: