24. 06. 13. Leaflet Number 671078

Installation and Maintenance

MEV-B Continuous Mechanical Extract Ventilation Units

Application arrangements
using balancing plates supplied

Bathroom

Main Room

Main Room

Main Room

Main Room

Main Room

Main Room

Main Room

Main Room

T2

T2 balancing plate fitted behind filter in one fan unit grille

Bathroom

T2

Main room and two  bathrooms

T2

Bathroom
en-suite

T2

Utility room

Utility room

T2

Main room with utility room and bathroom

T2

Bathroom

Bathroom

T2

T2

Main room and two bathrooms and water closet

T2

Bathroom

T2

Bathroom

Bathroom

T2

T1

T1

Main room with two bathrooms

T2

T2

Bathroom

Water Closet

T2

T2

T2 balancing plates fitted behind two filters in one fan 
unit grille. T1 balancing plate fitted behind filter in 
separate water closet

T1

Water Closet

T1 & T2

T2

Main room with additional utility room,  en-suite bathroom and water closet

T2

Bathroom

T2

Water Closet

T1 & T2

Utility room

T2

T2

Main room with  utility room,  bathroom and water closet
note alternative position of balancing plates

Bathroom

T2

Water Closet

T1 & T2

Utility room

T2

T1

Main room with utility room, bathroom and two water closets
note  positioning  of balancing plates

Bathroom

T2

Water Closet

T1 & T2

Water Closet

T1 & T2

Filter

Rear outlet
through outside wall
(Louvre etc not supplied)

En-suite bathroom
(Grille & filter supplied)

Inlet through 
unit filters

110 x 60
rectangular ducting
(by others)

Figure 4. Basic layout serving main room plus an en-suite 
bathroom.

Ducting lengths and bends

These should be kept to a minimum. Do not use flexible ducting. 

Do not use more than four 90

o

bends in any system.

Содержание MEV-B

Страница 1: ...reduce performance if necessary The unit is delivered with the BOOST speed adjustment set to 100 See the adjustments information on page 4 Coding MEV B Single fan unit MEV 2B Twin fan unit with auto...

Страница 2: ...it casing Connect the ductwork to the outlet spigot and fix the unit to the surface Any subsidiary inlet ductwork can now be connected to the unit Fitting a subsidiary inlet spigot The subsidiary inle...

Страница 3: ...it grille T1 balancing plate fitted behind filter in separate water closet T1 Water Closet T1 T2 T2 Main room with additional utility room en suite bathroom and water closet T2 Bathroom T2 Water Close...

Страница 4: ...y to full speed 100 The performance of the unit can be reduced if required by rotating the screw anti clockwise Fully anti clockwise will give 50 of the available duty Adjusting the Low Speed normal t...

Страница 5: ...nit is totally isolated from the electrical supply This is particularly important when dealing with a run on circuit as input socket terminals within these units remain live even when the room light o...

Страница 6: ...considered Lifting gear such as slings or ropes must be arranged so as not to bear on the casing 3 3 Equipment stored on site prior to installation should be protected from the weather and steps taken...

Страница 7: ...eded for dwellings assessed under The Building Regulations 2010 specifically SAP 2009 and Approved Documents L and F Completion of this document is therefore only required for dwellings assessed by SA...

Страница 8: ...ts diffusers or to overcome particular obstructions If flexible ducting has been used has it been pulled taut to minimise system resistance Has the number of duct bends been minimised to ensure adequa...

Страница 9: ...ave all the fans been mounted and installed inline with the IEE wiring regulations Has the unit been installed in a position that will permit access for maintenance purposes Have all grilles or ductwo...

Страница 10: ...lectrical Connection Decision Yes No or N A Has the rating label been verified to establish suitability for the installation strategy and whether an earth is required e g voltage class I or II product...

Страница 11: ...s having a minimum equivalent area of 2 500mm are fitted in each room except wet rooms from which air is extracted Where this approach causes difficulties e g on a noisy site seek expert advice Have t...

Страница 12: ...dvice Decision Yes No or N A Has the customer been supplied with suitable documentation detailing maintenance and operational requirements Has the customer been advised not to seal natural air flows f...