background image

Please ensure the unit is isolated before 

removing the cover.

Electrical connection

Note that the mains wiring for the unit MUST be from a fixed

wiring installation.

The fan is designed to be wired direct to the mains supply through

a fused spur isolator (by others).

It may be found easier to remove the terminal block and filter

grilles and any inlet spigots from the case to wire in the unit 

(See figure 6).

NB. The earth wire MUST be connected to the Earth post 

provided next to the block. (Figure 6). No earth is required to

the terminal block.

Refer to the electrical wiring diagram on page 5 when connecting

the unit. When the wiring is completed the unit can be 

re-assembled as follows:

The blower assembly complete with the electronic control module

can now be offered into the case. Push the module down to

locate the spade terminals into the block before fixing the blowers

to the back of the case. (Figure 5).

Note: Do NOT overtighten the blower retaining screws as the

fixing lugs may break if excessive force is used.

Warning: Before fitting the front cover ensure that the LEDs

on the module correctly align with the two small holes in the

cover. 

Refit any inlet grilles/spigots and ducting that was removed.

Test / Run the unit.

Adjusting the Full Speed (boost)

All the control functions and adjustments are located on the

Electronic Control Module.

The ‘Full Speed’ adjustment is located on the Electronic Control

Module (see figure 7). The adjustment range is 50 - 100% speed. 

Set to 100% for optimum performance.

Note the screw adjustment is pre-set at the factory to full

speed (100%).

The performance of the unit can be reduced if required by rotating

the screw anti-clockwise. (Fully anti-clockwise will give 50% of

the available duty).

Adjusting the Low Speed (normal) 
trickle ventilation

The ‘Low Speed’ adjustment (used for trickle ventilation) is located

on the Electronic Control Module (see figure 7).

The adjustment range is 0 - 50% speed. 

Note the screw 

adjustment is preset at the factory to zero and MUST BE SET

TO 25%.

The remote switch connection must be made in order to use the

‘BOOST’ facility. The switch terminals are numbered 3 and 1 on

the terminal block. (See wiring diagram).

Note: connection of a voltage source to these terminals will

damage the control module.

Run On Timer (not used)

A Run On Timer adjustment is also located on the Electronic

Control Module.  Its function is not required for this unit.

Note the unit is delivered with the run on timer screw set to

zero. The run on facility is not required in these applications

and should be left set at zero.

Electrical Data

Unit power consumption
(watts) @ full speed

MEVB        100 watts

MEV-2B     100watts

MEV-B+     200watts

Installation and Maintenance

MEV-B Continuous Mechanical Extract Ventilation Units 

Figure 7. Control adjustments on electronic module.

4

24. 06. 13. Leaflet Number 671078

Electrical
terminal 
block

Earth
post

Cable 
access

335

160 fixing ctrs

320

2

48 fixing ctrs

Blower assy
fixing inserts

Figure 6.  Internal view showing terminal block etc.

Electronic control
module

Run On Timer
(Not used)

Fail LED

Run LED

Low Speed
(trickle vent)
0 - 50%

Full Speed
50 - 100%

NORMAL

BOOST

Full load current 
(amps). 

MEV-B       0.39 amps

MEV-2B     0.39 amps

MEV-B+     0.78 amps

Cable 
access

Electronic
control
module

Blower assy
fixings

Figure 5.  Internal view showing blowers and electronic module.

Содержание MEV-B

Страница 1: ...reduce performance if necessary The unit is delivered with the BOOST speed adjustment set to 100 See the adjustments information on page 4 Coding MEV B Single fan unit MEV 2B Twin fan unit with auto...

Страница 2: ...it casing Connect the ductwork to the outlet spigot and fix the unit to the surface Any subsidiary inlet ductwork can now be connected to the unit Fitting a subsidiary inlet spigot The subsidiary inle...

Страница 3: ...it grille T1 balancing plate fitted behind filter in separate water closet T1 Water Closet T1 T2 T2 Main room with additional utility room en suite bathroom and water closet T2 Bathroom T2 Water Close...

Страница 4: ...y to full speed 100 The performance of the unit can be reduced if required by rotating the screw anti clockwise Fully anti clockwise will give 50 of the available duty Adjusting the Low Speed normal t...

Страница 5: ...nit is totally isolated from the electrical supply This is particularly important when dealing with a run on circuit as input socket terminals within these units remain live even when the room light o...

Страница 6: ...considered Lifting gear such as slings or ropes must be arranged so as not to bear on the casing 3 3 Equipment stored on site prior to installation should be protected from the weather and steps taken...

Страница 7: ...eded for dwellings assessed under The Building Regulations 2010 specifically SAP 2009 and Approved Documents L and F Completion of this document is therefore only required for dwellings assessed by SA...

Страница 8: ...ts diffusers or to overcome particular obstructions If flexible ducting has been used has it been pulled taut to minimise system resistance Has the number of duct bends been minimised to ensure adequa...

Страница 9: ...ave all the fans been mounted and installed inline with the IEE wiring regulations Has the unit been installed in a position that will permit access for maintenance purposes Have all grilles or ductwo...

Страница 10: ...lectrical Connection Decision Yes No or N A Has the rating label been verified to establish suitability for the installation strategy and whether an earth is required e g voltage class I or II product...

Страница 11: ...s having a minimum equivalent area of 2 500mm are fitted in each room except wet rooms from which air is extracted Where this approach causes difficulties e g on a noisy site seek expert advice Have t...

Страница 12: ...dvice Decision Yes No or N A Has the customer been supplied with suitable documentation detailing maintenance and operational requirements Has the customer been advised not to seal natural air flows f...

Отзывы: