Settings for primary airflow
17. Settings for primary airflow
The primary airflow should be set using the pressure
regulator (1) according to the required burner output.
The information given in the diagram can be used as
guide values.
Higher-viscosity fuels require higher air pressures.
18. Combustion air flow rate
Setting the combustion air flow rate (2).
Ideal values:
- Soot index according to Bacharach <1
- O
2
= 4 - 5%
The CO
2
values of a commercially available measuring in-
strument can only be used for processing the combustion
process for heating oil EL.
Flue gas temperature according to the operating instructions
of the heat generator.