Troubleshooting
23. Troubleshooting
Observation
Cause
Remedy
Burner does not start
up
Oil not combustible due to sludge and / or water
Oil tank empty
Oil level in burner tank too high
Filter dirty, oil or air lines leaky
Faulty feed pump solenoid valve
Nozzle dirty or faulty
Feed pump blocked
No current
Motor faulty
Thermostat faulty
Photocell dirty or not correctly inserted
Control unit faulty
No ignition
No compressed air
Solenoid valve faulty
Compressor or air line faulty
Open the water drain cock on the burner tank,
drain off sludge and water or
use a higher-grade heating oil
Refill tank with oil
Correct the oil level by draining off oil by means
of the water cock (readjust the level control
float switch, if necessary)
Clean the filter, feed pump filter and lines
Check the feed pump solenoid valve and
replace if necessary
Replace nozzle
Strip the feed pump and clean the gear
Switch on the heater switch
Replace
Replace
Clean the photocell, replace it or connect it
properly
Replace
Adjust the ignition electrode, replace the igni-
tion transformer if necessary and check the
ignition cable
Connect and/or open the compressed air and
set the pressure
Replace
Replace
Burner starts very late
Heating cartridge and thermocouple in burner
tank encrusted or faulty
Clean or replace the heating cartridge and
thermocouple in the burner tank
Burner starts without
pre-ventilating
Solenoid valve sticking in open position
Replace
No oil feed
Solenoid valve faulty
Replace
Flame is interrupted or
extinguishes
Oil not combustible due to sludge and / or water
Oil supply used up
Clogged nozzle
Dirty feed pump filter
Oil line to tank frozen
Supply tank to far away from burner
Filter or oil lines dirty
Solenoid valve faulty
Too much or not enough compressed air
Safety temperature limiter is in the safety posi-
tion because the heater has overheated
Micro-switch in burner tank cuts out
Open the water drain cock on the burner tank,
drain off sludge and water or use higher-grade
oil
Refill tank with oil
Replace nozzle
Clean feed pump filter
Clean oil lines, and insulate tank and oil line
Install an additional feed pump
Replace filter and clean oil lines
Replace
Check compressed air and gauge pressure
using primary airflow control
Troubleshoot the heater and unlock the safety
temperature limiter
Adjust the level control float
Nozzle and baffle plate
are heavily soiled with
oil or soot
Incorrect baffle plate setting
Combustion airflow rate too high or too low
Boiler room is not sufficiently ventilated
Correct the baffle plate setting dimensions
Set the primary airflow rate
Set the secondary airflow rate at the air control
flap
Pay attention to sufficiently large ventilation
ports