background image

6

E

.0

4.

20

00

 •

 G

. 1

6.

11

.1

0

Oil pump

12. Oil pump

The oil pumps serve as delivery units, pumping oil into the burner tank. The atomisation of the oil is not
dependent on the oil pressure.

Suntec oil pump:

 

= feed

  = return

  = pressure pipe connection

  = pressure measuring connection

= vacuum measuring connection

  = pressure adjustment 

13. Installing the oil line

Install oil lines, filters and floating suction unit from the supply pump to the supply tank.
For installation in the open air or on outside walls, the lines must be specially insulated or fitted with addi-
tional pipe heaters, as otherwise the water contained in the oil will freeze causing the oil to become highly
viscous.

14. Setting the ignition electrodes

The ignition electrodes are preset. The specified dimensions (Fig.) are for checking purposes.

1

2

3

4

6

5

4

Содержание G100 Universal

Страница 1: ...G100 Universal Oil Burner Installation Maintenance Manual...

Страница 2: ...ge and burner 5 10 Connecting to power supply 5 11 Compressed air connection 5 12 Oil pump 6 13 Installing the oil line 6 14 Setting the ignition electrodes 6 15 Control unit 7 16 Table of settings 8...

Страница 3: ...mounting unit separate operating instructions technical information flange seal Near wear free compressed air atomising nozzles are pre fitted at the factory 3 Operating instructions This technical i...

Страница 4: ...mbustion process The burner blower supplies the secondary air which is added to the atomised spray at the baffle plate This ensures full combustion and operational reliability At the oil temperature i...

Страница 5: ...it as indicated in the wiring diagram HEED LOCAL REGULATIONS Use flexible wiring Overcurrent protection configuration The overcurrent protection devices must be rated for the electrical current range...

Страница 6: ...adjustment 13 Installing the oil line Install oil lines filters and floating suction unit from the supply pump to the supply tank For installation in the open air or on outside walls the lines must b...

Страница 7: ...llowing a mains power failure The control unit indicates a fault if an external light source is detected during the pre aeration cycle after expiration of the safety cycle The control unit may only be...

Страница 8: ...deviate Adjustment is required in any case due to the system design For initial start up fill the burner tank up to the oil mark by hand Caution If the oil level is too high the float switch will swi...

Страница 9: ...an be used as guide values Higher viscosity fuels require higher air pressures 18 Combustion air flow rate Setting the combustion air flow rate 2 Ideal values Soot index according to Bacharach 1 O2 4...

Страница 10: ...a flue gas thermometer The higher the flue gas temperature the greater the flue gas loss Rising flue gas temperatures indicate increasing deposits that will reduce the degree of combustion effi cienc...

Страница 11: ...thermostat STB H11 Ext status lamp H13 Ext fault indication lamp K1 Relay M1 Burner motor P11 Ext operating hours counter Q1 Heater power switch S1 Micro switch overflow protection S2 Level micro swit...

Страница 12: ...in burner tank encrusted or faulty Clean or replace the heating cartridge and thermocouple in the burner tank Burner starts without pre ventilating Solenoid valve sticking in open position Replace No...

Страница 13: ...13 E 04 2000 G 16 11 10 Exploded view drawing spare parts list 24 Exploded view drawing spare parts list ZBZ_2 278...

Страница 14: ...4 x 10 x 2 50 37 50 10788 27 Solenoid valve R1 4 SV04 1 36 90 11583 27 Solenoid valve coil 1 47 90 24686 28 Thread reducing adaptor 1 4 1 8 1 47 90 11303 29 Solenoid valve oil tank connecting tube 1 4...

Страница 15: ......

Страница 16: ...G100 Universal Oil Burner 07 11 Enertech Limited P O Box 1 Vines Lane Droitwich Worcestershire WR9 8NA tel 44 0 1905 794331 fax 44 0 1905 794017 email info nu way co uk web www nu way co uk...

Отзывы: