11.0 Sequence of operation
The following is the normal sequence of operation for the trinity boiler.
Trinity Sequence of operation
Boiler in
standby mode
Indirect thermostat
or flow switch closes A-C
((Call for Domestic))
Thermostat, End switch
or relay closes T-C
((Call for Heat))
Combi
or
Indirect
Displays version
t2.0
120v Power
Applied
Awaiting
Input
A-C Closed
Energizes
3-way diverter
valve
Energizes Primary
Pump (C1)
Indirect
Water
Heater
Energizes Indirect Pump
(Ap) turns off C1
Combi Model
Sentry 2100
((Call for Ignition))
Air
Switches
Sentry 2100
Open
Error
A S O
Closed
Sentry 2100
Fan to SFS (75)
24 Vlot signal
to blower
Sentry 2100
Error
A S C
Three
Retries
for Flame
Closed
Power to Ignitor
120V to S1
Flame Probe
Signal < 1 micro A
Less than
1.0 microA
Power to Gas Valve
Sentry 2100
Modulates Fan
based upon setpoint
and programing
Open
Greater than 1.0 microA
Prepurge
Call for flame ends
24VAC from Sentry
B1 to Fenwal W
Energizes Primary
Pump (C1)
Igniter warm-up
5 seconds