background image

 

29

10.0 TROUBLE SHOOTING 

This section is intended to assist the service technician in detecting and correcting common errors. The 
Sentry 2100 is equipped with an internal diagnostic system that verifies control operation. The following 
series of error codes has been developed to aid in diagnosing control problems: 
 

Problem

 

Detected Problem 

Solution 

ER1

  

On Display 

 

The Safety High Limit of 250

°

 F, has been 

reached 

1- Check to see if water is dripping on the sensor. 
 2- Reduce the Hi setting (and/or) ensure that there is 
proper water circulation in the system. 

ER2 

On Display 

 

Water Probe… The water probe is transmitting 

an invalid signal. Closed circuit. 

Check wiring 

ER3  

On Display 

 

Water probe…Sentry is sensing an open circuit 

at water probe.  Or, the wiring to the outdoor 

probe is grounding. 

Check wiring.  (Note: ER3 will be displayed if 
temperature sensed is less then 32

°

F.) 

Note: If problem is corrected by resetting power, Sentry 
control had locked-up; contact NY Thermal. 

ER5

  

On Display 

 

DHW 

Problem 

The control has determined an Indirect water 

heater problem, the boiler has cycled off 10 times 

during a single call for domestic. The Indirect call 

will now be ignored until power is reset or the 

indirect call is interrupted. 

((Not activated on Combi version)) 

1-Not enough flow to keep boiler from tripping on limit. 
Verify that a min. of 6 GPM flow is going through boiler & 
indirect circuit.  
2- Reduce indirect Aquastat setting, or Increase 
difference between (Lo Setting) and (indirect Aquastat 
setting).  
3- Indirect limit or wiring failure. 

ER6 

“Flame Lock Out” 

 

Sentry has sensed a lack of 24V to the gas valve 

during operation or a Fenwal ignition lockout. 

1- There is a problem in the ignition sequence, it could be 
caused by a faulty igniter, flame sensor, gas valve or 
improper line pressure or combustion.  Check ignition 
sequence to determine which component is not 
functioning.  

(Sentry will retry ignition sequence 1 hour 

after ER6 code originally occurs or if control is reset) 

2- Check for 24V between B on terminal block and F1 on 
Sentry plug, if not present a limit has tripped (see wiring 
diagram). 

Reset calculation being used to lower HI setting. 

If OD probe is being used, the HI setting will be 
calculated using formula in Section 8. 

Burner 

shuts off 

before set-

point 

temperature 

is reached 

(and burner 

light goes out)

 

Thermostat is satisfied 

1-If the thermostat demand light is turning off, the 
thermostat has satisfied. 
2-If DHW temp light is turning off; the aquastat or call for 
domestic has been satisfied. 

 

ASO 

Indicates 

that the Air 

Switch is 

Open 

This is displayed when the boiler is expecting the 

air switch to be closed by a differential pressure 

generated when the combustion blower turns on.  

It can occur momentarily during normal 

operation. A problem is indicated when ASO is 

displayed continuously. 

 1-Are the vinyl tubes connected between the air switch 
and the ports on the inlet pipe.  Negative side of switch 
connects to the port on the 1-1/2 ABS elbow. 
 2-Check for blockage on the intake and exhaust vents. 
 3-If fan is running, air switch may be faulty. 
 4-If fan is not running, check 120V wiring to blower, if ok 
remove low voltage harness from blower, if blower fails to 
start, replace blower, if blower does start problem may be 
with blower or Sentry control. 

 

ASC 

Indicates 

that the Air 

Switch is 

Closed

 

 

This is displayed when the boiler has turned the 

blower off and is expecting the air switch to be 

open.  It can occur momentarily during normal 

operation. A problem is indicated when ASC is 

displayed continuously. 

 1-Is the fan running. If so check for 24V between C and 
D terminals (see wiring diagram).  If 24V is not present 
replace transformer.   
 2-Check venting termination with required venting 
described in manual. 
 

Ignition 

Sequence 

not 

Check for 24 Volts between terminal B1 on 

Sentry & Ground 

 1 – If there is 24V, indicates faulty wiring between BI and 
W1 on Fenwal, or faulty Fenwal. 
 2 – If 24V is not present proceed to next step. 

Содержание Trinity Ti 150

Страница 1: ...different temperatures 16 6 3 DOMESTIC COMBI SYSTEM OPTIONAL 17 7 0 WIRING 19 7 1 SIMPLIFIED WIRING CONNECTIONS 20 7 2 ADVANCED WIRING SYSTEMS 21 7 2 1 Multiple 4 wire Zone Valves 21 7 2 2 Multiple Z...

Страница 2: ...s Dimensions L W D Inches 22 5 15 25 14 22 5 15 25 17 25 Clearance to Combustibles 0 1 1 High Altitude Operation The Trinity boiler is designed to operate to capacity in installations with 2000 feet o...

Страница 3: ...ponents are protected from dripping or spraying water or rain during operation and servicing The boiler location ambient temperature is maintained to a minimum of 50 F Determine the best location of t...

Страница 4: ...ation of 30 is required 24 12 12 so increase minimum vertical separation by 12 18 12 30 If horizontal distance is greater then 6 no additional vertical spacing is required Vertical separation is never...

Страница 5: ...terials Vent Piping A C See Chart for maximum lengths 3 ABS solid core 3 PVC Sch 40 3 CPVC Sch 40 pipe 3 AL29 4C Rigid Stainless Vent Air Supply Vent B See Chart for maximum lengths 3 ABS 3 PVC Sch 40...

Страница 6: ...18 12 Plus Snow Must insert plastic bird screen Must be 1 from wall Support Field installed Inlet air Exhaust Inlet air Exhaust Support Field supplied Exhaust 24 Inlet Air Exhaust Inlet Air Roof weat...

Страница 7: ...wall for more rigidity 6 In all roof applications the discharge must point away from the pitch of the roof 7 Install adequate flashing where the pipe enters the roof to prevent water leakage 8 Install...

Страница 8: ...lates sweep and 45 elbows and 90 elbows at 5 equivalent feet IMPORTANT The length of one vent pipe intake or exhaust may not exceed the length of the other vent pipe by more then 20 equivalent feet Th...

Страница 9: ...ate of Massachusetts the condensate must be neutralized prior to entering a drain The following are important notes that must be taken into consideration when constructing the condensate system DO NOT...

Страница 10: ...ifold pressure should occur when any unit or combination of units lights or runs Always use a pipe threading compound that is resistant to propane LP gas solvent action Use sparingly to all male threa...

Страница 11: ...t all of the plumbing system externally Do not apply torque to the boiler fittings Hold the fitting when installing otherwise damage to the unit will occur The Trinity boiler employs a pneumatic modul...

Страница 12: ...M 6 45 F NRF 33 UP 26 64 0010 Ti200 10 at 8 GPM 8 45 F PL 36 UP 26 99 0011 Relief Valve 30PSI Is provided with the system and it is to be mounted as shown in the diagram Ensure that the discharge of t...

Страница 13: ...lied to the boiler Circuit is 120 Volts 12 Amps The Trinity boiler is to be used only in a Primary Secondary pumping system This is to avoid cycling problems in systems that have poor flow or heating...

Страница 14: ...Combi Manifold 82470 1 Primary Loop For Combi Model Only Ti200 N O F Ti200 relief valve location All other piping is same as Ti150 Primary Loop For Heating Model Quantity and location of shutoff valve...

Страница 15: ...ltiple Zones using Zone Valves 6 2 2 Multiple Zones using Pumps Zone 1 Zone 2 Zone 3 Normally closed 4 wire Zone Valves With End Switches Primary Loop Max 12 apart See figure 7 2 1 Multiple 4 wire Zon...

Страница 16: ...pump controller By setting the tempering valves to different settings multiple temperatures can be obtained Installer may require throttling and check valves to correctly regulate the system Other co...

Страница 17: ...e prior to installing the flange COMBI Sequence of operation When water flow greater than 5 GPM passes through the flow switch it closes a contact to terminals A C on the Sentry 2100 controller The bo...

Страница 18: ...using extremely hard water at high temperatures In such cases it is always possible to clean the exchanger by circulating a cleaning liquid Use a tank with weak acid 5 phosphoric acid or if the excha...

Страница 19: ...t off valve fully 2 Turn the dial on the mixing valve to the desired setting being careful not to exceed 120 F or a dial setting greater then 2 and adjust LO setting accordingly 3 Create the maximum a...

Страница 20: ...electrical leaks that could damage the board Before providing 120 Volts to the boiler do a polarity check of the line and neutral wires line must be connected to black and neutral must be connected t...

Страница 21: ...ses circuit to zone valve motor thus opening the valve When the valve is opened the end switch closes the circuit between terminals T C on the Sentry control The Sentry 2100 provides power to the prim...

Страница 22: ...ion Room thermostat closes circuit to TT terminals Taco ZVC403 to ZVC 406 zone controller The controller energizes the appropriate zone valve and closes the circuit between terminals T C on the Sentry...

Страница 23: ...ntroller The controller energizes the appropriate circulating pump and closes the circuit between terminals T C on the Sentry control The Sentry 2100 provides power to the primary pump C1 once the pum...

Страница 24: ...to the injection pump through the 356 Tekmar controller 3 Closes the circuit between terminals T C on the Sentry control The Sentry 2100 provides power to the primary pump via C1 once the pump is on...

Страница 25: ...powered off and on Sentry Display The following describes the meaning of the lights on the Sentry controller Green Lights Burner Bruleur Indicates that the ignition system is activated Circ Indicates...

Страница 26: ...ted on the bottom side of the control Function and To enter the programming mode press the function key once To scroll through the various menu options depress until the menu is displayed To alter the...

Страница 27: ...ting is only used during a call for DHW when A C terminals are closed Set the LO to the temperature you require for the Indirect Water Heater recommend 140 F or at least 30 F higher than the indirect...

Страница 28: ...a pilot It is equipped with an ignition device that automatically lights the burner Do not try to light the burner by hand B BEFORE OPERATING check all around the appliance area for gas Be sure to che...

Страница 29: ...Sentry will retry ignition sequence 1 hour after ER6 code originally occurs or if control is reset 2 Check for 24V between B on terminal block and F1 on Sentry plug if not present a limit has tripped...

Страница 30: ...es on Fenwal Indicates Ignition Lockout Reset Boiler so it will attempt to ignite Check for proper operation of ignition components Make sure igniter glows and gas valve opens Check for proper line pr...

Страница 31: ...sed the gas line must not create any forces to the valve either vertically weight of line or horizontally misaligned connection The following are the thermister curves for diagnosing the water and out...

Страница 32: ...ve Energizes Primary Pump C1 Indirect Water Heater Energizes Indirect Pump Ap turns off C1 Combi Model Sentry 2100 Call for Ignition Air Switches Sentry 2100 Open Error A S O Closed Sentry 2100 Fan to...

Страница 33: ...pressures See Section 5 2 2 Turn gas shut off valve to the ON position 3 Turn Power on to boiler MV S2 W S1 L1 L2 GND 1 8 4 5 6 7 A 2 1 3 8 6 5 2 3 4 7 L2 C T L1 B1 F1 Ap C1 BLOWER 5 4 3 2 1 GROUND TR...

Страница 34: ...stion fan is noise vibration free 2 The condensate freely flows from the unit and is cleaned of sediment 3 Relief Valve and air vents are not weeping 4 Low water cut off is flushed if applicable 5 Exa...

Страница 35: ...at shield 10 82762 Rauscchert Flame Rod 11 82763 Composit Flue Box 11A 82764 Composit Flue Box Gasket 11B 82765 Composit Flue Outlet Gasket 11C 82100 2 Clamp 11D 82748 2 ABS Coupling adaptor 12 82659...

Страница 36: ...boiler D Decision of warranty repairs or replacements to boiler will be at the discretion of the manufacturer or authorized service representative E Corrosion or pitting of the heat exchanger caused b...

Отзывы: