Chapter 6 Commissioning
NR ELECTRIC CO., LTD.
65
Table 6.3-1 Power supply range of
RCS-9698G/H
Rated Voltage
3 options to be selected:
110V/125V DC;
220V/250V DC;
48V DC
Variation
(80% ~ 120%)Un
It should be noted that the device can withstand an AC ripple of up to 15% of the upper rated
voltage on the DC auxiliary supply.
WARNING:
Energize the device only if the auxiliary supply is within the specified
operating ranges.
6.3.2 With the Device Energized
The following groups of checks verify that the hardware and software is functioning correctly and
should be carried out with the power supply applied to the device.
6.3.2.1 Testing the
“
STANDBY”LED Indicators
After
RCS-9698G/H
is energized and finishes starting up,
the green “
STANDBY
”
LED
on the
MASTER MACHINE
will be lit off,
the green “
STANDBY
”
LED
on the
STANDBY MACHINE
will be lit on.
6.3.2.2 Testing the LED Indicators of CPU/COM/MDM board
If a
CPU/COM/MDM
board operates normally, the corresponding green “
HEALTHY
”
LED
will be lit
on and the corresponding green “
ALARM
”
LED
will be lit off.
If any error is detected in a
CPU/COM/MDM
board during operation, the corresponding green
“
HEALTHY
”
LED
will be lit off and the corresponding red “
ALARM
”
LED
will be lit on.
If any
IED
is linked to an
RS-232/422/485
serial port, an ethernet or a
MOMEM
port of
RCS-9698G/H
, the corresponding “
ACT
”
LED
will be lit on.
If some data are transmitted and received via a port, the corresponding “
ACT
”
LED
will flash.
6.3.3 Communication Function Testing
RCS-9698G/H
should be used together with the
RCS-9798 Configuration Tool
, the
RCS-9798
Debugging Tool
and the control center simulation tools for communication function testing.
6.3.4 Final Check
After the above tests are completed, remove all test or temporary shorting leads, etc. If it has been
necessary to disconnect any of the external wiring from the device in order to perform the wiring
verification tests, it should be ensured that all connections are replaced in accordance with the
relevant external connection or scheme diagram.
Содержание RCS-9698G
Страница 1: ...RCS 9698G H Remote Terminal Unit Instruction Manual NR Electric Co Ltd...
Страница 2: ......
Страница 6: ...RCS 9698G H Remote Terminal Unit NR ELECTRIC CO LTD iv...
Страница 10: ...RCS 9698G H Remote Terminal Unit NR ELECTRIC CO LTD viii...
Страница 72: ...Chapter 5 Installation NR ELECTRIC CO LTD 62 ground terminal of this device...
Страница 76: ...Chapter 6 Commissioning NR ELECTRIC CO LTD 66...