Chapter 3 Hardware Structure and Operation Theory
NR ELECTRIC CO., LTD.
12
1) 110V/125V DC;
2) 220V/250V DC;
3) 48V DC.
The Pin connections of these 3 PWR modules are the same.
PWR
board must be configured in
RCS-9698G/H
.
PWR
board can only be equipped in slot 1.
RCS-9698G
has 1
PWR
board.
RCS-9698H
has 2
PWR
boards, each side of
RCS-9698H
has 1
PWR
board.
WARNING: PWR
board may only be withdrawn or inserted when the power supply is
switched off. To withdraw a board, turn off the switch of the power supply and disconnect
the green power supply cable connector. Other modules may only be withdrawn or
inserted when the power supply is switched off.
Front view of the
PWR
board is shown in the following figure.
6
4
5
3
12
10
11
9
7
8
18
16
17
15
13
14
2
1
20
19
GND
PWR +
BO_GEN.
ALARM
BI_ RESV1
OPTO-
PWR
RESV
RESV
PWR -
RESV
RESV
BO_FAIL
BO_GEN.
FAULT
BO_MASTER
BI_ REMOTE
BI_ RESV2
BI_ RESV3
Figure 3.3-1
PWR
board
There is a 20-pin male connector in the front of the
PWR
board. The terminal definitions of the
connectors are described as below.
Table 3.3-1 Pin description of
PWR
board
Содержание RCS-9698G
Страница 1: ...RCS 9698G H Remote Terminal Unit Instruction Manual NR Electric Co Ltd...
Страница 2: ......
Страница 6: ...RCS 9698G H Remote Terminal Unit NR ELECTRIC CO LTD iv...
Страница 10: ...RCS 9698G H Remote Terminal Unit NR ELECTRIC CO LTD viii...
Страница 72: ...Chapter 5 Installation NR ELECTRIC CO LTD 62 ground terminal of this device...
Страница 76: ...Chapter 6 Commissioning NR ELECTRIC CO LTD 66...
Страница 80: ...Chapter 8 Decommissioning and Disposal NR ELECTRIC CO LTD 70...