N1020 Temperature Controller 

NOVUS AUTOMATION 

4/8 

The display alternates the presentation of the parameter prompt and 

its value. The parameter value is displayed with a light blinking to 

differentiate it from the parameter prompt.  
Depending on the level of parameter protection adopted, the 

parameter PASS precedes the first parameter in the level where the 

protection becomes active. See section CONFIGURATION 

PROTECTION. 
At the end of this manual, a table with the complete sequence of 

levels and parameters is presented. 

DESCRIPTION OF THE PARAMETERS 

OPERATION LEVEL 

PV 

PV indication 

Timer 

Timer  remaining time.  Only shown when the Timer 

function is in use. (

T1me

 

 0) (HH:MM). 

SP

 

Control SP adjustment. 

T1me 

Sets the Timer, 00:00 to 99:59 (HH:MM). 

Rate

 

RATE OF PV RISE: from the current PV to the SP value. 

In degrees/minute.  

rvn 

Enables control outputs and alarms. 

YES

 

- Outputs enabled. 

NO

 

- Outputs disabled. 

f.key

  -“F” key assumes control over the RUN 

command.  

TUNING LEVEL 

Atvn 

Auto-tune 

Defines the control strategy to be taken:  

off

  – Turned off. (no PID tuning)  

Fast

–  Fast

 

automatic tuning.  

Full

–  More accurate automatic tuning.  

self

–  P auto - adaptative tuning 

rslf

–  Forces one new precise automatic p 

auto - adaptative tuning.  

TGht

 -  Forces one new precise aut auto - 

adaptative tuning when Run = YES or 

controller is turned on.  

Refer to the “DETERMINING PID PARAMETERS” 

section for further details on tuning strategies.

 

pb 

Proportional  

Band 

Proportional Band -

 

Value of the term P  of the control 

mode PID, in percentage of the maximum span of the 

input type. Adjust of between 0 and 500.0 %. 
Select zero for ON/OFF control. 

ir 

Integral Rate 

Integral Rate - Value of the term I of the PID algorithm, in 

repetitions per minute (Reset). Adjustable between 0 and 

99.99. 
Displayed only if proportional band 

 0. 

dt 

Derivative Time 

Derivative Time – Value of the term D of the control mode 

PID, in seconds. Adjustable between 0 an 300.0 seconds. 
Displayed only if proportional band 

 0. 

(t

 

Level Time 

Pulse Width Modulation (PWM) period in seconds. 

Adjustable between 0.5 and 100.0 seconds.  
Displayed only if proportional band 

 0.  

kyst 

Hysteresis 

Control Hysteresis (in engineering. units): This parameter 

is only shown for ON / OFF control (Pb=0). Adjustable 

between 0 and the measurement input type span.  

A(t 

Action

 

Control Action: For Auto Mode only. 

re

  Control with Reverse Action. Appropriate heating

Turns control output on when PV is below SP. 

dir

  Control  with  Direct  Action.  Appropriate  for 

cooling.  Turns control output on when PV is 

above SP. 

sfst 

Softstart 

SoftStart Function  –: Time in seconds during which the 

controller limits the MV value progressively from 0 to 100 

%. It is enabled at power up or when the control output is 

activated. If in doubt set zero (zero value disables the 

Soft start function). 

0ut1 
0ut2 

Outputs 1 and 2 function: 

Off

  not used; 

(trl

  control output. 

A1  

Alarm 1. 

A2  

Alarm 2. 

A1a2 

Alarm 1 AND Alarm 2 at the same time. 

ALARMS LEVEL 

Fva1

 

Fva2

  

Function Alarm 

Functions of Alarms. Defines the functions for the alarms 

among the options of the Table 02

Sp.a1

  

Sp.a2 

Alarm Setpoint: Tripping points for alarms 1 and 2. Value 

that defines the point of activation for the programmed 

alarms with the functions 

Lo

 or 

ki

For the alarms configured with Differential  type 

functions, this parameter defines deviation (band).  
Not used for the other alarm functions. 

 

bla1

 

bla2

  

Blocking Alarm 

Block Alarm 1 and 2: This function blocks the alarms 

when the controller is energized. 

YES

 - enables initial blocking  

 

NO

  - inhibits initial blocking  

xya1

 

xya2

  

Hysteresis of Alarm 

Alarm Hysteresis. Defines the difference between the 

value of PV at which the alarm is triggered and the value 

at which it is turned off. 

A1t1 
A2t1 

Alarm Time t1 

Defines the temporization time t1, for the alarms.  

In seconds. 

A1t2 
A2t2 

Alarm Time t2 

Defines the temporization time t2, for the alarms.  

In seconds. 

flsh 

 

Allows you to identify the occurrence of alarm conditions 

by flashing the PV indication on the display screen. 

YES

- Enables alarm signaling flashing PV 

NO 

- Disables alarm signaling flashing PV 

CONFIGURATION LEVEL 

Type 

Type

 

Input Type: Selects the input signal type to be connected 

to the process variable input. Refer to Table 1  for the 

available options. 

fltr 

Filter

 

Digital Input Filter -  Used to improve the stability of the 

measured signal (PV). Adjustable between 0 and 20. In 0 

(zero) it means filter turned off and 20 means maximum 

filter. The higher the filter value, the slower is the response 

of the measured value. 

Dp.po 

Decimal Point 

Selects the decimal point position to be viewed in both 

PV and SP.  

vn

i

 t 

Unit

 

Unit. Temperature indication in °C or °F. Not shown for 

linear inputs.   

0ffs 

Offset

 

Sensor Offset: Offset value to be added to the PV 

reading to compensate sensor error.  
Default value: zero.  

Spll 

SP Low  Limit 

Defines the SP lower limit. 
To 0-50 mV input type sets the lower range for SP and PV 

indication. 

Spxl 

SP High Limit 

Defines the SP upper limit. 
To 0-50 mV input type sets the upper range for SP and PV 

indication. 

T1me 

Timer

 

Time. Adjustment.  00:00 to 99:59 (HH:MM). 
(same function as the one presented in the operation 

level) 

Содержание N1020

Страница 1: ...nsult the DEVICE MANAGER in the Windows CONTROL PANEL to identify the COM port that was assigned to the controller Consult the mapping of the MODBUS memory in the controller s communications manual an...

Страница 2: ...the value of measured PV is above the value defined for alarm Setpoint SPA1 PV dif Alarm of Differential Value In this function the parameters SPA1 and SPA2 represent the deviation of PV in relation...

Страница 3: ...ine trimming the PV indication to compensate for sensor errors Default value zero SERIAL COMMUNICATION For full documentation download the Registers Table N1020 for Serial Communication on our web sit...

Страница 4: ...opriate for cooling Turns control output on when PV is above SP sfst Softstart SoftStart Function Time in seconds during which the controller limits the MV value progressively from 0 to 100 It is enab...

Страница 5: ...fications carried out by the user ovll Output Low Limit Lower limit for the control output Minimum percentage value assumed by the control output when in automatic mode and in PID Typically configured...

Страница 6: ...E indication on the display It is recommended not to turn the controller off neither change the SP during this learning period It is recommended not to turn the controller off neither change the SP du...

Страница 7: ...tion with a Pt100 simulator pay attention to the simulator minimum excitation current requirement which may not be compatible with the 0 170 mA excitation current provided by the controller N1020 PARA...

Страница 8: ...PR OUT1 Pulse OUT2 Relay B Digital Communication 485 Interface communication RS485 C Power Supply Nothing shown 100 240 Vac 48 240 Vdc 50 60 Hz 24V 12 24 Vdc 24 Vac SAFETY INFORMATION Any control sys...

Отзывы: