background image

N1020 Temperature Controller 

NOVUS AUTOMATION 

2/8 

ELECTRICAL CONNECTIONS 
The controller complete set of features is drawn in Fig.  01. The 

features loaded in a particular unit are shown on its label: 

 

Fig. 01 - Connections of the back panel 

FEATURES 

INPUT TYPE SELECTION 
Select the input type (in parameter “

tYPE

”) from Table 01 below. 

TYPE 

CODE 

RANGE OF MEASUREMENT 

Tc j 

Range: -110 to 950 ºC (-166 to 1742 ºF) 

Tc k 

Range: -150 to 1370 ºC (-238 to 2498 ºF) 

Tc t 

Range: -160 to 400 ºC (-256 to 752 ºF) 

Tc n 

Range: -270 to 1300 ºC (-454 to 2372 ºF) 

Tc r 

Range: -50 to 1760 ºC (-58 to 3200 ºF) 

Tc s 

Range: -50 to 1760 ºC (-58 to 3200 ºF) 

Tc b 

Range: 400 to 1800 ºC (752 to 3272 ºF) 

Tc e 

Range: -90 to 730 ºC (-130 to 1346 ºF) 

Pt100 

Pt 

Range: -200 to 850 ºC (-328 to 1562 ºF) 

0 to 50 mV 

L0.50 

Linear. Programmable indication -1999 to 9999 

Table 01 - Input Types 

OUTPUTS 
The N1020 offers two output channels, user configurable as Control 

outputAlarm 1 output or Alarm 2 output.  
OUT1 -  Logical pulse, 5 Vdc / 25 mA, available at terminals 4 and 5. 
OUT2 -  Relay SPST-NA, 1.5 A / 240 Vac, available at terminals 6 

and 7. 

Note: The outputs can be configured independently from each other, 

for example, both can be control outputs at the same time. 

CONTROL OUTPUT 
The control strategy can be configured as ON / OFF or PID

ALARM OUTPUT 
There two alarms available in the N1020. The alarms can be 

assigned to either output, logical or relay. The alarm functions are 

described below. 

ALARM FUNCTIONS 
The alarms can be configured to operate with nine different functions, 

as shown in Table 02

off

 

Alarms turned 

Off

lo

 

Alarm of Absolute Minimum Value. Triggers when the value of 

measured PV is below the value defined for alarm Setpoint 

(SPA1 or SPA2)

 

SPA1 

PV 

  

ki

 

Alarm of Valor Absolute Maximum Value. Triggers when the 

value of measured PV is above the value defined for alarm 

Setpoint

 

SPA1 

PV 

 

dif

 

Alarm of Differential  Value. In this function the  parameters 

SPA1

 and 

SPA2

 represent the deviation of PV in relation to 

the SP of CONTROL. 

 

SP 

PV 

SP + SPA1 

SP – SPA1 

 

 

SP 

PV 

SV – SPA1 

 

 

SV + SPA1 

 

 

SPA1 positive 

SPA1 negative 

difl

 

Alarm of Minimum Differential Value. It triggers when the value 

of PV is  below  the defined point by  (using the Alarm 1 as 

example): 

 

SP 

PV 

SP – SPA1 

 

 

SP 

PV 

SP – SPA1 

 

SPA1 positive 

SPA1 negative 

difk

 

Alarm of Valor Maximum Differential Value. Triggers when the 

value of PV is above the defined point by (using Alarm 1 as 

example): 

 

SP 

PV 

SP + SPA1 

 

 

SP 

PV 

SP + SPA1 

 

SPA1 positive 

SPA1 negative 

t.0n

 

Timer ON alarm. Sets alarm output ON when timer is runing.  

t.end

 

Timer end. Configures the alarm to actuate when the timer 

expires. 

ierr

 

Sensor Break Alarm. Activated when the input signal of PV is 

interrupted, out of the range or when Pt100 in short-circuit. 

Table 02 – Alarm functions 

Alarms Timer Modes (Temporization) 
The controller alarms can be configured to perform 4 timer modes: 

MODE 

A1t1

 

a2t1

 

A1t2 

A2t2

 

ACTION 

Normal 

Operation 

 

Alarm Event 

Alarm 

Output 

 

Activation for 

a defined time 1 to 6500 s 

Alarm Event

Alarm

Output

T1

 

Activation with 

delay 

1 to 6500 s 

 

Alarm Event 

Alarm 

Output 

T2 

 

Intermittent 

Activation  1 to 6500 s 1 to 6500 s 

Alarm Event

Alarm

Output

T1

T2

T1

 

Table 03 - Temporization Functions for the Alarms 

The signs associated to the alarms will light when the alarm condition 

is recognized, not following the actual state of the output, which may 

be temporarily OFF because of the temporization. 
Initial Blocking of Alarm 
The initial blocking option inhibits the alarm from being recognized if 

an alarm condition is present when the controller is first energized (or 

after a transition from run YES 

NO). The alarm will be enabled 

only after the occurrence of a non alarm condition followed by a new 

occurrence for the alarm. 

Содержание N1020

Страница 1: ...nsult the DEVICE MANAGER in the Windows CONTROL PANEL to identify the COM port that was assigned to the controller Consult the mapping of the MODBUS memory in the controller s communications manual an...

Страница 2: ...the value of measured PV is above the value defined for alarm Setpoint SPA1 PV dif Alarm of Differential Value In this function the parameters SPA1 and SPA2 represent the deviation of PV in relation...

Страница 3: ...ine trimming the PV indication to compensate for sensor errors Default value zero SERIAL COMMUNICATION For full documentation download the Registers Table N1020 for Serial Communication on our web sit...

Страница 4: ...opriate for cooling Turns control output on when PV is above SP sfst Softstart SoftStart Function Time in seconds during which the controller limits the MV value progressively from 0 to 100 It is enab...

Страница 5: ...fications carried out by the user ovll Output Low Limit Lower limit for the control output Minimum percentage value assumed by the control output when in automatic mode and in PID Typically configured...

Страница 6: ...E indication on the display It is recommended not to turn the controller off neither change the SP during this learning period It is recommended not to turn the controller off neither change the SP du...

Страница 7: ...tion with a Pt100 simulator pay attention to the simulator minimum excitation current requirement which may not be compatible with the 0 170 mA excitation current provided by the controller N1020 PARA...

Страница 8: ...PR OUT1 Pulse OUT2 Relay B Digital Communication 485 Interface communication RS485 C Power Supply Nothing shown 100 240 Vac 48 240 Vdc 50 60 Hz 24V 12 24 Vdc 24 Vac SAFETY INFORMATION Any control sys...

Отзывы: