N1020 Temperature Controller 

NOVUS AUTOMATION 

5/8 

Tm.en 

Timer Enable

 

Shows a copy of the Timer parameter in the operating 

level. 

En  

 - enables 

T1me

 parameter to the operating  

   level 

Dis 

- doesn’t show the 

T1me

 parameter in the 

  operating level 

T.str 

Timer Start

 

Defines the mode for starting the Timer. 

sP

 - when PV reach the temperature value in SP 

rvn

  - when RUN →YES 

f.rst

  - “F” key (reset timer) 

f.stp

  - “F” key (start/stop the timer). 

T.e.(.0 

Timer End Control 

Off

 

Control behavior when the timer expires: 

YES

  

- disables the outputs (RUN = NO). 

NO

     - outputs continue to operate. 

Rate

 

Ramp function. Establishes the rate of increase of PV, in 

degrees/minute. 
Same 

Rate

 

function as showed in the operating level. 

rT.en 

Rate  Enable

 

Shows a copy of the Rate

 

parameter in the operating 

level. 

En

     - enables the 

Rate

 parameter to the  

operating level. 

Dis

 

- doesn’t show the 

Rate

 parameter in the 

 operating level 

rvn 

 Enables the control and alarm outputs. 

YES

 

- outputs enabled. 

NO

 

- outputs disabled. 

f.key

  -  outputs enabled/disabled function  assigned 

   to the F key. 

Same 

rvn

 

function as showed in the operating level. 

rv.en 

Run Enable

 

Shows a copy of the 

rvn

 

parameter in the operating level. 

En

    -  enables the 

rvn

 

parameter in the operating 

level 

Dis

 -  doesn’t show the 

rvn

 

parameter in the 

operating level 

bavd 

Baud Rate

 

Baud Rate da comunicação serial. Em kbps 
1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6 e 115.2  

prty 

Parity

 

Paridade da comunicação serial. 

 

none

  Sem paridade 

 

Ewem

  Paridade par 

 

0dd

  Paridade impar 

Addr 

Address

 

Endereço de Comunicação. Número que identifica 

o controlador na rede de comunicação serial, entre 

1 e 247. 

CALIBRATION LEVEL 
All of the input and output types are calibrated in the factory. If a 

recalibration is required, this should be carried out by a 

experienced personnel. If this level is accidentally accessed, pass 

through all the parameters without pressing the 

 

 or   keys  

pass 

Password 

Input of the Access Password.  
This parameter is presented before the protected levels. 

See item Protection of Configuration

(alib 

Calibration? 

Enables or disables instrument calibration by the user,  

   YES:  shows calibration parameters 

   No:  Hides the calibration parameters  

inL( 

Input Low 

Calibration 

See section MAINTENANCE / Input Calibration.  

Enter the value corresponding to the low scale signal 

applied to the analog input.  
Only showed if 

(alib

 

= YES 

ink( 

Input High 

Calibration 

See section MAINTENANCE / Input Calibration.  

Enter the value corresponding to the full scale signal 

applied to the analog input. 
Only showed if 

(alib

 

= YES 

rstr 

Restore

 

Restores the factory calibration for all inputs and outputs, 

disregarding modifications carried out by the user. 

ovll 

Output Low Limit 

Lower limit for the control output - Minimum percentage 

value assumed by the control output when in automatic 

mode and in PID. Typically configured with 0 %. Default 

value: 0 % 

ovkl 

Output High Limit 

Upper limit for the control output - Maximum percentage for 

the control output when in automatic mode and in PID.  

Typically configured with 100 %. Default value: 100 %. 

(j 

Cold Junction 

Cold junction temperature controller. 

Pas.( 

Password 

Change

 

Allows defining a new access password, always different 

from zero. 

Prot 

Protection 

Sets up the Level of Protection. See Table 04

Freq 

Frequency 

Mains frequency. This parameter is important for proper 

noise filtering. 

snk 

Shows the four first digits of the controller serial number. 

snL

 

Shows the four last digits of the controller serial number. 

CONFIGURATION PROTECTION 

The controller provides means for protecting the parameters 

configurations, not allowing modifications to the parameters values, 

avoiding tampering or improper manipulation. The parameter 

Protection  (

PROt

), in the Calibration level, determines the 

protection strategy, limiting the access to particular levels, as shown 

by the Table 04

Protection 

Level 

Protection Levels 

Only the Calibration level is protected. 

Calibration and Tuning levels. 

Calibration, Tuning and Alarms levels 

Calibration, Tuning, Alarms and Configuration levels 

Calibration, Tuning, Alarms, Configuration levels 

Table 04 – Levels of Protection for the Configuration 

ACCESS PASSWORD 
The protected levels, when accessed, request the user to provide the 

Access Password  for granting permission to change the 

configuration of the parameters on these levels. 
The prompt 

PASS

 precedes the parameters on the protected levels. 

If no password is entered, the parameters of the protected levels can 

only be visualized. 
The  Access  Password is defined  by the  user  in  the parameter 

Password Change  (

PAS.(

), present  in  the Calibration Level.  The 

factory default for the password code is 1111. 

PROTECTION ACCESS PASSWORD 
The protection system built into the controller blocks for 10 minutes 

the access to protected parameters after 5 consecutive frustrated 

attempts of guessing the correct password. 

MASTER PASSWORD 
The Master Password is intended for allowing the user to define a 

new password in the event of it being forgotten. The Master 

Password doesn’t grant access to all parameters, only to the 

Password Change  parameter (

PAS(

). After defining the new 

password, the protected parameters may be accessed (and 

modified) using this new password. 
The master password is made up by the last three digits of the serial 

number of the controller added to the number 9000. 
As an example, for the equipment with serial number 07154321, the 

master password is 9 3 2 1. 

Содержание N1020

Страница 1: ...nsult the DEVICE MANAGER in the Windows CONTROL PANEL to identify the COM port that was assigned to the controller Consult the mapping of the MODBUS memory in the controller s communications manual an...

Страница 2: ...the value of measured PV is above the value defined for alarm Setpoint SPA1 PV dif Alarm of Differential Value In this function the parameters SPA1 and SPA2 represent the deviation of PV in relation...

Страница 3: ...ine trimming the PV indication to compensate for sensor errors Default value zero SERIAL COMMUNICATION For full documentation download the Registers Table N1020 for Serial Communication on our web sit...

Страница 4: ...opriate for cooling Turns control output on when PV is above SP sfst Softstart SoftStart Function Time in seconds during which the controller limits the MV value progressively from 0 to 100 It is enab...

Страница 5: ...fications carried out by the user ovll Output Low Limit Lower limit for the control output Minimum percentage value assumed by the control output when in automatic mode and in PID Typically configured...

Страница 6: ...E indication on the display It is recommended not to turn the controller off neither change the SP during this learning period It is recommended not to turn the controller off neither change the SP du...

Страница 7: ...tion with a Pt100 simulator pay attention to the simulator minimum excitation current requirement which may not be compatible with the 0 170 mA excitation current provided by the controller N1020 PARA...

Страница 8: ...PR OUT1 Pulse OUT2 Relay B Digital Communication 485 Interface communication RS485 C Power Supply Nothing shown 100 240 Vac 48 240 Vdc 50 60 Hz 24V 12 24 Vdc 24 Vac SAFETY INFORMATION Any control sys...

Отзывы: