![Novus LogBox-BLE Скачать руководство пользователя страница 24](http://html1.mh-extra.com/html/novus/logbox-ble/logbox-ble_instruction-manual_1712942024.webp)
NOVUS AUTOMATION
24/57
○
Maximum Interval: 18 hours.
MEMORY MODE
•
Circular Memory:
Allows you to select so that the device continuously logs in memory. When the memory is full, the oldest data will be erased
so that the most recent data can be saved.
•
Memory Full:
Allows you to select the device to pause records when the internal memory has no more available space.
START MODE
•
Immediate Start:
Allows you to select to have the logs started shortly after the device is reconfigured.
•
Date/Time:
Allows configuring the date/time at which the logs are to be started.
•
By Keyboard:
Allows you to enable a screen in the display where you can change the status of registrations to
enabled
. Therefore, the logs will
be started at that time.
•
By Digital Input:
Allows you to configure it so that the logs start from the digital input. This parameter is only available if the digital input is
enabled and configured for Log Control, so that the logs are started the moment the digital input is triggered. The log edge shall be configured in
the digital input parameters.
•
By Software:
Provides permission for the logs to be started by a command from
NXperience-BLE
or
NXperience
.
•
Daily:
Allows a schedule to be configured so that logs are started every day at the configured time. A Daily log start mode also requires a Daily
log end mode.
STOP MODE
•
Memory Mode Only:
Allows the configuration chosen for the Memory Mode to dictate the logs behavior: if Full Memory is chosen, the logs will
end as soon as there is no more memory space; if Circular Memory is chosen, the logs will continue indefinitely.
•
Date/Time:
Allows the user to configure the date/time at which the logs are to be stopped.
•
By Keyboard:
Allows you to enable a screen in the display where you can change the status of registrations to disabled. Therefore, the logs will
be stopped at that time.
•
By Digital Input:
Allows you to configure so that the logs are stopped from the digital input. This parameter is only available if the digital input is
enabled and configured for Log Control, so that the logs are stopped the moment the digital input is triggered. The log edge shall be configured
in the digital input parameters.
•
By Software:
Provides permission for the logs to be stopped by a command from
NXperience-BLE
or
NXperience
.
•
Daily:
Allows a schedule to be configured so that logs are stopped every day at the configured time. A Daily log stop mode also requires a Daily
log start mode.
The combinations allowed for starting and ending logs are as follows:
Start Mode
End Modes
Immediate
Memory Mode or Date/Time or by Keyboard or Software or Digital Input
Date/Time
Memory or Date/Time or by Keyboard or Software or Digital Input
Digital Input
Memory or Digital Input
Keyboard
Memory or Keyboard
Software
Memory or Software
Daily
Daily
Table 05